| Plan Review Notes For Permit 21120578 |
| Permit Number |
21120578 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-05 16:10:15 | FAILED | | | | | | 1) THIS LOCATION IS WITHIN A HISTORIC DISTRICT. PLEASE | | | PROVIDE A COPY OF THE STATE HISTORIC PRESERVATION | | | OFFICE APPROVAL OF THIS LOCATION. | | | | | | 2) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. | | | THE POLE COLOR IS TO MATCH THE COLOR OF THE DECORATIVE | | | CONCRETE LIGHT POLE ADJACENT TO THE PROPOSED POLE | | | LOCATION. | | | | | | 3) THE PLANS SHOW A GAS LINE AND UNDERGROUND ELECTRIC | | | WITHIN 2 FEET OF THE POLE CAISSON AND THE BORE PIT FOR | | | THE UNDERGROUND ELECTRIC. IN ORDER TO VERIFY THAT THE | | | INSTALLATION WILL NOT INTERFERE WITH THE EXISTING | | | FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO | | | OBJECTION FROM FPU REGARDING THE INSTALLATION. | | | | | | 4) PROVIDE CROSS SECTIONS OF THE LOCATION OF THE | | | UNDERGROUND ELECTRIC FOR THE FULL LENGTH OF THE | | | INSTALLATION. THERE UNDERGROUND ELECTRIC MUST BE | | | CLEARLY SHOWN AVOIDING THE STREET TREE ROOT SYSTEMS AND | | | ANY INFRASTRUCTURE THAT IT CROSSES (EX: THE GAS LINE). | | | | | | 5) THE SURVEY NEEDS TO SHOW THE SAME UNDERGROUND | | | ELECTRIC PATH AS THE POWER ROUTE PLAN. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|