| 2022-03-10 16:57:47 | INSUFFICIENT |
| | |
| | 1) THE PROPOSED POLE IS SHOWN IN FRONT OF THE SINGLE |
| | FAMILY HOUSED THAT ARE LOCATED ON THE EAST SIDE OF |
| | POINSETTIA AVENUE. THE SITE PLAN WITH AERIAL SHOWS THAT |
| | THE POLE IS DIRECTLY IN FRONT OF HOUSE ON THE PROPERTY |
| | AT 2704 POINSETTIA AVENUE. THE POLE NEEDS TO BE SHIFTED |
| | TO THE NORTH AT LEAST THREE FEET TO BE LOCATED NORTH OF |
| | THE NORTH WALL OF THE HOUSE. |
| | |
| | 2) THE CITY CODE REQUIRES THAT POLES SHALL BE LOCATED |
| | SO AS TO ALIGN WITH EXISTING POLES IN THE RIGHT-OF-WAY |
| | AND HAVE EQUAL SETBACK DISTANCES WITH EXISTING POLES |
| | FROM THE CURBLINE OF THE RIGHT-OF-WAY. THE PROPOSED |
| | POLE IS NOT SHOWN IN LINE WITH THE EXISTING LIGHT POLES |
| | ALONG TAMARIND AVENUE IN THIS LOCATION. THE POLE NEEDS |
| | TO BE MOVED A COUPLE FEET TO THE WEST. |
| | |
| | 3) THE BORE PIT, BY THE POLE, NOTES ON SHEET P-1 STATE |
| | THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, IT IS |
| | LOCATED ONLY WITHIN THE PARKWAY WHICH WILL NEED |
| | RESTORATION. PLEASE UPDATE THE NOTATIONS ACCORDINGLY. |
| | |
| | 4) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC |
| | WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH |
| | EXISTING UTILITIES. |
| | |
| | 5) THE PLANS SHOW GAS AND COM LINES ADJACENT TO THE |
| | BORE PIT(S). IN ORDER TO VERIFY THAT THE INSTALLATION |
| | WILL NOT INTERFERE WITH THE EXISTING FACILITIES, |
| | PROVIDE A PUBLIC UTILITY LETTER OF NO OBJECTION FROM |
| | FPU FOR THE GAS LINE AND THE COM PROVIDER(S), MOST |
| | LIKELY AT&T OR COMCAST. |
| | |
| | 6) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. |
| | THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP |
| | 7042 TRAFFIC GREY A. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | [email protected] |
| | |
| | |