| Notes |
| Date |
Text |
| 2022-06-23 17:19:43 | 1) PROPOSED ELECTRIC ROUTE DOES NOT APPEAR TO BE IN | | | CONFLICT WITH CITY UTILITIES HOWEVER CITY UTILITIES ARE | | | SHOWN INCORRECTLY ON PLANS. INCLUDE CITY UNDERGROUND | | | UTILITIY PIPE SIZE, PIPE MATERIAL, AND DESCRIPTION ON | | | THE SITE PLAN. CONTACT JANICE TARBILL, [email protected] | | | FOR AS-BUILT INFORMATION. INCLUDE AS-BUILT INFORMATION | | | IN YOUR RESUBMITTAL. | | | 2) PROVIDE PROFILE FOR PROPOSED UNDERGROUND ELECTRIC | | | SHOWING ALL CROSSING DATA FOR OTHER UTILITIES. | | | 3) ALL ROADWAY, SIDEWALK, AND SWALE RESTORATIONS ARE | | | REQUIRED PER CITY STANDARD. | | | | | | SUZANNE BERGLUND | | | [email protected] | | | 561-494-1075 | | | |
|