Plan Review Notes
Plan Review Notes For Permit 21120564
Permit Number 21120564
Review Stop B
Sequence Number 3
Notes
Date Text
2023-01-18 15:54:06BUILDING REVIEW APPROVED WITH PROVISO:
 1-ENERGY CALCULATIONS ARE TAKING THE HEAT RECOVERY UNIT
 (HRU) CREDIT. SEE ITEM #16(B) ON ENERGY CALCULATIONS.
 PLANS DON'T SPECIFY HEAT RECOVERY UNIT. NEED TO REVISE
 EITHER THE ENERGY CALCULATIONS OR PLANS TO SHOW
 COMPLIANCE WITH SEC. R405.7.7 FBC-ENERGY CONSERVATION
 TO TAKE THIS CREDIT.