2022-07-20 16:49:07NEW SINGLE FAMILY RESIDENCE(R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21120564 518 COLONIAL RD
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL
 THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED
 AGENT TO AVOID CONFLICT/DELAYS.
  
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED;
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM. NEED
 OWNER'S NAME, BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C)CEILING R-30 VALUE SPECIFIED ON PAGE 3 IS INCORRECT.
 IT DOESN'T MATCH INFORMATION ENTERED ON PAGE 1. REVISE
 AS REQUIRED TO MATCH. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 D)WINDOWS OVERHANG SEPARATION SPECIFIED ON PAGE 4 IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 3- BEDROOM EGRESS WINDOWS DON'T COMPLY WITH THE MINIMUM
 CLEAR OPENING REQUIREMENTS OF SEC. R310.2.1
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 NOTE: COORDINATE SIZE OF WINDOW WITH PRODUCT APPROVAL
 TO AVOID CONFLICTS/DELAYS.
  
 RESPONSE:
 REVISED SHEET A-2 WAS NOT RESUBMITTED. UNABLE TO SEE
 CHANGES STATED ON ENGINEER'S RESPONSE LETTER. EGRESS
 WINDOW COMMENT WAS FOR BEDROOM #1, I APOLOGIZE FOR NOT
 BEING SPECIFIC ON MY PREVIOUS COMMENT.
 FOR CLARIFICATION SINGLE HUNG WINDOWS (2'-6"X4'-1")
 DON'T COMPLY WITH ALL THE EGRESS REQUIREMENTS OF SEC.
 R310.2.1 FBC-RESIDENTIAL, INCLUDING MINIMUM CLEAR
 HEIGHT.
 NOTE: IF SPECIFYING CASEMENT WINDOWS, THEN CLEARLY
 SPECIFY EGRESS HINGE. DEPENDING ON THE WINDOW SIZE NOT
 ALL CASEMENT WINDOWS COMPLY, EXCEPT FOR THOSE WITH THE
 EGRESS HINGE PROVIDING THE MINIMUM CLEAR WIDTH.
  
 4- OK.
 5- OK.
  
 ORIGINAL COMMENT:
 6- SPECIFY ATTIC ACCESS SIZE. SEC. R807.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REVISED SHEET A-2 WAS NOT RESUBMITTED. UNABLE TO SEE
 CHANGES STATED ON ENGINEER'S RESPONSE LETTER.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
  
 RESPONSE:
 PRODUCT APPROVALS WERE NOT SUBMITTED FOR REVIEW ON THE
 FIRST SUBMITTAL. COPIES OF PRODUCT APPROVALS ARE ALWAYS
 REQUIRED TO BE SUBMITTED FOR REVIEW. LISTING THE NOA OR
 FLORIDA PRODUCT APPROVAL NUMBER ON DRAWINGS DOESN'T
 SATISFY THIS REQUIREMENT. COMMENTS BELOW APPLY TO THOSE
 PRODUCT APPROVALS SUBMITTED THIS TIME.
  
 A)EXTERIOR DOORS AS SHOWN ON PLANS.
  
 RESPONSE:
 PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. NEED TO
 PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL, INCLUDING
 THE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO THE DRAWINGS SUBMITTED. NOTE: THE
 FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS
 IF PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT.
 CHAPTER 553 F.S.
 NOTE: THERE ARE THREE DIFFERENT PRODUCT APPROVALS
 SUBMITTED. ONE IS A MIAMI DADE NOA AND THE OTHER ONES
 ARE TWO FLORIDA PRODUCT APPROVALS. CLARIFY WHICH ONES
 ARE GOING TO BE INSTALLED AND WHERE. FOR EXAMPLE, ENTRY
 DOOR OR BEDROOM #2.
  
 B)WINDOWS.
  
 RESPONSE:
 CASEMENT WINDOWS NOA 20-0402.02 SUBMITTED IS
 INCOMPLETE. ONLY THE COVER PAGE WAS SUBMITTED. NEED TO
 SUBMIT COMPLETE PRODUCT APPROVAL.
  
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
  
 RESPONSE:
 MULLION SIZE WAS NOT SPECIFIED.
  
 D)ROOF SHINGLES. OK.
  
 E)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. OK.
  
 ORIGINAL COMMENT:
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 THERMA-TRU FLORIDA PRODUCT APPROVAL LISTED ON SHEET S-2
 DOESN'T MATCH THOSE UPLOADED TO PROJECTDOX. COORDINATE
 WITH ITEM #7(A) AND REVISE AS REQUIRED TO MATCH.
  
 ORIGINAL COMMENT:
 9- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ENGINEER IS
 SPECIFYING R-20 SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THIS FOAM TO VERIFY COMPLIANCE
 WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE THE
 REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 RESPONSE:
 ONLY THE MANUFACTURER'S INSTALLATION INSTRUCTIONS WAS
 PROVIDED. NEED TO SUBMIT THE ACTUAL ICC CURRENT
 EVALUATION REPORT AS REQUESTED.
  
 10- OK.
 11- OK.
 12- OK.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]