| 2022-04-01 18:15:29 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21120564 |
| | |
| | 1-LOT DRAINAGE. PROPOSED WORK AFFECTS THE LOT DRAINAGE. |
| | PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE |
| | IS KEPT WITHIN THE LOT AND NOT DIVERTED TO ADJACENT |
| | PROPERTIES. PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE |
| | WITH THE FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. |
| | SEC. 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY |
| | AMENDMENTS. |
| | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| | ADJACENT PROPERTIES. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.5 FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL |
| | THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED |
| | AGENT TO AVOID CONFLICT/DELAYS. |
| | |
| | 3- BEDROOM EGRESS WINDOWS DON'T COMPLY WITH THE MINIMUM |
| | CLEAR OPENING REQUIREMENTS OF SEC. R310.2.1 |
| | FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | NOTE: COORDINATE SIZE OF WINDOW WITH PRODUCT APPROVAL |
| | TO AVOID CONFLICTS/DELAYS. |
| | |
| | 4- SPECIFY ALL ROOF LIVE AND DEAD LOADS. CLEARLY |
| | SPECIFY TRUSS TOP AND BOTTOM CHORDS LIVE AND DEAD LOADS |
| | INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE |
| | R301.5 FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G". |
| | |
| | 5-REVISE ROOF SHEATHING NOTE ON THE LEFT HAND SIDE OF |
| | THE ROOF PLAN ON SHEET S-2. NEED TO USE RING SHANK |
| | NAILS AND ROOF SHEATHING NEEDS TO BE NAILED WITH AT 4 |
| | INCHES O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC. |
| | R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL. REVISE |
| | SPECIFICATIONS OR PROVIDE CALCULATIONS SHOWING THAT |
| | SPECIFIED NAIL TYPE AND SPACING MATCHES OR EXCEEDS |
| | TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM REQUIREMENTS. |
| | NOTE: REVISE NOTES ON ROOF SHEATHING ATTACHMENT DETAIL |
| | ON SAME SHEET ALSO. |
| | |
| | 6- SPECIFY ATTIC ACCESS SIZE. SEC. R807.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | A)EXTERIOR DOORS AS SHOWN ON PLANS. |
| | B)WINDOWS. |
| | C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO AVOID DELAYS/CONFLICTS). |
| | D)ROOF SHINGLES. |
| | E)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. |
| | |
| | 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 9- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ENGINEER IS |
| | SPECIFYING R-20 SPRAY INSULATION. PROVIDE ICC |
| | EVALUATION REPORT FOR THIS FOAM TO VERIFY COMPLIANCE |
| | WITH SEC. R316 FBC-RESIDENTIAL. |
| | NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE THE |
| | REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 10-PROVIDE BOUNDARY SURVEY SHOWING THE PROPOSED |
| | BUILDING SETBACKS AS REQUIRED BY SEC. 107.2.5 CITY |
| | AMENDMENTS. |
| | |
| | 11- SHEET S-2: MARK OF TRUSS ANCHOR SHOWN ON THE TRUSS |
| | ANCHOR SCHEDULE DOESN'T MATCH MARK SHOWN ON THE ROOF |
| | PLAN. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 12- SITE PLAN SHEET A-1 WAS NOT SIGNED AND SEALED BY |
| | THE ENGINEER OF RECORD. ALL DRAWINGS NEED TO BE SIGNED |
| | AND SEALED AS REQUIRED BY CHAPTER 471 F.S. WHEN |
| | SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS. |
| | NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH ENGINEER'S |
| | DIGITAL SIGNATURE OR PROVIDE HARD COPY PLANS WITH |
| | ORIGINAL SEAL AND SIGNATURE |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |