2022-01-24 15:30:01DOOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF
 THE DOOR REPLACEMENT - SHOW DOOR SIZE - SHOW DIMENSION
 FROM THE CORNER OF THE BUILDING TO THE EDGE OF THE DOOR
 OPENING - THIS INFORMATION IS REQUIRED TO DETERMINE THE
 WIND ZONE 4 OR 5
  
 2) PLEASE PROVIDE THE COMPLETE PRODUCT APPROVAL - FRONT
 PAGES AND THE INSTALLATION INSTRUCTIONS.
  
 3) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 NEEDS TO INCLUDE LABOR AND THE COST OF THE DOOR AS IF A
 CONTRACTOR IS GOING TO INSTALL IT. WHEN RE SUBMITTING
 PLEASE ADD THE ADDITIONAL COST ON THE RESUBMITTAL FORM
 IN THE SPACE PROVIDED.
  
 4) PRODUCT APPROVAL PROVIDED IS FOR A NON IMPACT DOOR -
 WHEN REPLACING DOORS WITH GLAZING THEY NEED TO MEET
 IMPACT REQUIREMENTS - A SHUTTER WILL BE REQUIRED FOR
 THIS SLIDING GLASS DOOR - PLEASE PROVIDE THE SHUTTER
 PRODUCT APPROVAL.
  