| Plan Review Notes For Permit 21120532 |
| Permit Number |
21120532 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-02-10 12:30:45 | 2ND ELECTRIC REVIE FAILED | | | ELECTRIC REVIEW COMMENTS 2-7 HAVE BEEN ADEQUATELY | | | ADDRESSED | | | 1) COMMENT # 1 HAS NOT BEEN ADDRESSED . CONDUCTOR | | | AMPACITY MUST BE BASED ON 75 DEGREE C AS PER NEC | | | 110.14(C)(1)(B)(1).350 CU MCM AMPACITY DETAILED AS | | | 310-AMPS NEC 310.15(B)(16) THREE SETS OF CONDUCTORS | | | DOES NOT PROVIDE ADEQUATE AMPACITY FOR 1000-AMP | | | SERVICE. NEC 240.4(C). PLEASE CORRECT AS NESSECARY. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|