Plan Review Notes
Plan Review Notes For Permit 21120532
Permit Number 21120532
Review Stop E
Sequence Number 1
Notes
Date Text
2022-01-04 10:12:27ELECTRICAL PLAN REVIEW FAILED
 1) RISER DIAGRAM SHOWS WIRE SIZE FOR SERVICE ENTRANCE
 AND CONDUCTORS FED FROM A 1000-AMP ADJUSTABLE TRIP
 BREAKER TO BE (3) SETS OF 350 KCMIL WIRE. IF ASSUMED
 THE CONDUCTOR IS COPPER (THE RISER DOES NOT STATE SUCH)
 THE AMPACITY AT 75 DEGREE C IS 310- AMPS. 310X 3 =
 930-AMPS. NEC 210.240.4 (C) STATES CONDUCTORS WITH
 OVERCURRENT DEVICES OVER 800-AMPS TO BE SIZED EQUAL TO,
 OR ABOVE THE RATING OF THE OVERCURRENT DEVICE. PLEASE
 CORRECT THE SIZE OF THE CONDUCTORS OR BREAKER SETTINGS
 TO BE CODE COMPLIANT
 2) THE LABELING ON THE SERVICE MAIN STATES MAIN 3 OF 3.
 IF THIS SERVICE IS THE ONLY ONE FEEDING THIS STRUCTURE,
 PLEASE RE-LABEL IT ACCORDINGLY AND, OR, SHOW ALL OTHER
 SERVICES THAT EXIST AND ARE TO REMAIN.
 3) DRAWING DO NOT STATE AVAILABLE FAULT CURRENT
 AVAILABLE FOR EQUIPMENT AND SPD DEVICES AS PER NEC
 110.10, 110.24 AND NEC 285.7
 4) PLEASE PROVIDE NOTES STATING, ?ARC FLASH? LABELING
 IS TO BE INSTALLED AS PER NEC 110.16
 5) PLEASE SHOW LOCATION OF PANEL ?B? ON SHEET ?E-3? FBC
 107.2
 6) PLEASE CHANGE AC PANEL SCHEDULES TO REFLECT PANELS
 C-H, NOT C-J. FBC 107.2
 7) PLEASE PROVIDE SPECIFICATIONS FOR EMERGENCY LIGHTING
 THAT CONFORMS TO 2020 FBC 1008.1
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  