| 2022-01-04 10:12:27 | ELECTRICAL PLAN REVIEW FAILED |
| | 1) RISER DIAGRAM SHOWS WIRE SIZE FOR SERVICE ENTRANCE |
| | AND CONDUCTORS FED FROM A 1000-AMP ADJUSTABLE TRIP |
| | BREAKER TO BE (3) SETS OF 350 KCMIL WIRE. IF ASSUMED |
| | THE CONDUCTOR IS COPPER (THE RISER DOES NOT STATE SUCH) |
| | THE AMPACITY AT 75 DEGREE C IS 310- AMPS. 310X 3 = |
| | 930-AMPS. NEC 210.240.4 (C) STATES CONDUCTORS WITH |
| | OVERCURRENT DEVICES OVER 800-AMPS TO BE SIZED EQUAL TO, |
| | OR ABOVE THE RATING OF THE OVERCURRENT DEVICE. PLEASE |
| | CORRECT THE SIZE OF THE CONDUCTORS OR BREAKER SETTINGS |
| | TO BE CODE COMPLIANT |
| | 2) THE LABELING ON THE SERVICE MAIN STATES MAIN 3 OF 3. |
| | IF THIS SERVICE IS THE ONLY ONE FEEDING THIS STRUCTURE, |
| | PLEASE RE-LABEL IT ACCORDINGLY AND, OR, SHOW ALL OTHER |
| | SERVICES THAT EXIST AND ARE TO REMAIN. |
| | 3) DRAWING DO NOT STATE AVAILABLE FAULT CURRENT |
| | AVAILABLE FOR EQUIPMENT AND SPD DEVICES AS PER NEC |
| | 110.10, 110.24 AND NEC 285.7 |
| | 4) PLEASE PROVIDE NOTES STATING, ?ARC FLASH? LABELING |
| | IS TO BE INSTALLED AS PER NEC 110.16 |
| | 5) PLEASE SHOW LOCATION OF PANEL ?B? ON SHEET ?E-3? FBC |
| | 107.2 |
| | 6) PLEASE CHANGE AC PANEL SCHEDULES TO REFLECT PANELS |
| | C-H, NOT C-J. FBC 107.2 |
| | 7) PLEASE PROVIDE SPECIFICATIONS FOR EMERGENCY LIGHTING |
| | THAT CONFORMS TO 2020 FBC 1008.1 |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |