| Notes |
| Date |
Text |
| 2022-07-18 09:59:26 | 05/04/22 TALKED TO CHRIS MACRI. OK TO PROVISO. JG. | | | | | | BUILDING REVIEW APPROVED WITH PROVISO. | | | (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS): | | | | | | 1- DEFERRED SUBMITTALS: | | | A)ALL WINDOW TYPES SHOWN ON PLANS. | | | B)ALL DOOR TYPES SHOWN ON PLANS. | | | C)ROOF TILE AS SHOWN ON PLANS. NOTE: CLEARLY SPECIFY | | | FASTENING. | | | | | | 2-ALL PRODUCT APPROVALS TO BE APPROVED IN WRITING BY | | | DESIGNER OF RECORD. | | | | | | 3- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-30 | | | INSULATION. | | | NOTE: ARCHITECT TO APPROVE THE REPORT IN WRITING PRIOR | | | TO SUBMITTAL. | | | | | | 4-SUBMIT COMPLETE INFORMATION FOR THE PERIMETER | | | CONCRETE WALL UNDER A SEPARATE PERMIT. SEC. 105.1 CITY | | | AMENDMENTS. |
|