| Plan Review Notes For Permit 21120514 |
| Permit Number |
21120514 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-14 14:36:38 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21120514 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | ACCESSORY STRUCTURE: | | | 1) PLEASE SHOW ALL DOORS IN THE HEATED AREA. PLEASE | | | SHOW HOW THE BEDROOM WILL BE HEATED WHILE THE DOOR IS | | | CLOSED. FBC R303.10 | | | | | | 2) THE DRYER EXHAUST DUCT SHALL BE A MINIMUM THICKNESS | | | OF 28 GAUGE. FBC RES M1502.4.1 | | | | | | | | | PROMARY RESIDENCE: | | | | | | 1) THE DRYER EXHAUST DUCT SHALL BE A MINIMUM THICKNESS | | | OF 28 GAUGE. FBC RES M1502.4.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|