Plan Review Notes
Plan Review Notes For Permit 21120493
Permit Number 21120493
Review Stop G
Sequence Number 2
Notes
Date Text
2022-04-25 18:21:482ND REVIEW FBC-2020 RES. GAS
 PERMIT- 21120493
 4/25/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST
 REVIEW HAS NOT BEEN COMPLETELY ADDRESSED. NOTES HAVE
 BEEN ADDED FOR FURTHER CLARIFICATION.
  
 1) FAILED ITEMS A & B. SHEETS P0.1 & P0.2: BASED ON THE
 INCREASED 423,000 BTU LOAD PIPE SIZING FOR THE SYSTEM
 MUST BE RE-EVALUATED. PLEASE REFER TO SEC. G2412.3 &
 G2412.4 FBC RES, AND PROVIDE THE FOLLOWING INFORMATION:
  
 A) FAILED. THE LENGTH OF THE BRANCH LINE TO THE GAS
 GRILL AND THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM
 THE METER TO THE MOST REMOTE OUTLET- SEC. G2413.4.1 FBC
 RES.(TOTAL DEVELOPED LENGTH NOT PROVIDED.)
  
 B) FAILED. THE SIZES AND LENGTHS OF THE SCHEDULE 40
 METALLIC FROM THE METER TO THE PE- TABLE G2413.4(2) FBC
 RES. (NOT PROVIDED. PLEASE NOTE THAT BASED ON TABLE
 402.4(5) AND AN APPROXIMATE 125 TOTAL DEVELOPED LENGTH,
 A MINIMUM 1-INCH DIAMETER SCHEDULE 40 MAIN SUPPLY PIPE
 IS REQUIRED.)
  
 2) FAILED. P0.1 & P0.2: REFER TO TABLE G2413.4(8) FBC
 RES- BASED ON THE PIPE LENGTHS SHOWN IT APPEARS THE
 3/4-INCH PE BRANCH LINE SERVING THE POOL HEATER,
 GENERATOR AND GAS GRILL IS UNDERSIZED AND MUST BE
 INCREASED TO A MINIMUM 1-INCH PIPE. (THE PE PIPE HAS
 BEEN INCREASED TO 1-INCH PE, HOWEVER THE REVISED RISER
 DRAWING SHOWS THE FOLLOWING DEFICIENCIES:)
  
 A) THE LOW PRESSURE 1-INCH AND 1/2-INCH CSST ARE
 UNDERSIZED PER TABLE 402.4(15) WHICH IS PRINTED ON
 SHEET P0.1. BASED ON THE APPROX. 55 FT. TOTAL DEVELOPED
 LENGTH OF THE LOW PRESSURE RUN FROM THE REGULATOR TO
 THE GRILL AND TABLE 402.4(15) THE 1-INCH PIPE SHALL BE
 INCREASED TO 1-1/2-INCH AND THE 1/2-INCH SHALL BE
 INCREASED TO 1-1/4-INCH.
  
 B) PLEASE INDICATE THE TYPES AND SIZES OF PIPING FROM
 THE LOW PRESSURE REGULATOR TO THE GENERATOR AND TO THE
 POOL HEATER- SEC. 402.3 FBC FG.
  
 3) FAILED. P0.1 & P0.2: PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALL MANUAL FOR THE NEW GAS
 GRILL- SEC. G2408.1 FBC RES. THE SPECS AND INSTALLATION
 INSTRUCTIONS HAVE BEEN SUBMITTED. REFER TO VENTILATION
 REQUIRMENTS IN THE MANUAL AND SHOW THE LOCATIONS AND
 SIZES OF UPPER AND LOWER VENTS REQUIRED FOR VENTILATION
 AND COMBUSTION AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  