| 2022-04-25 18:21:48 | 2ND REVIEW FBC-2020 RES. GAS |
| | PERMIT- 21120493 |
| | 4/25/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST |
| | REVIEW HAS NOT BEEN COMPLETELY ADDRESSED. NOTES HAVE |
| | BEEN ADDED FOR FURTHER CLARIFICATION. |
| | |
| | 1) FAILED ITEMS A & B. SHEETS P0.1 & P0.2: BASED ON THE |
| | INCREASED 423,000 BTU LOAD PIPE SIZING FOR THE SYSTEM |
| | MUST BE RE-EVALUATED. PLEASE REFER TO SEC. G2412.3 & |
| | G2412.4 FBC RES, AND PROVIDE THE FOLLOWING INFORMATION: |
| | |
| | A) FAILED. THE LENGTH OF THE BRANCH LINE TO THE GAS |
| | GRILL AND THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM |
| | THE METER TO THE MOST REMOTE OUTLET- SEC. G2413.4.1 FBC |
| | RES.(TOTAL DEVELOPED LENGTH NOT PROVIDED.) |
| | |
| | B) FAILED. THE SIZES AND LENGTHS OF THE SCHEDULE 40 |
| | METALLIC FROM THE METER TO THE PE- TABLE G2413.4(2) FBC |
| | RES. (NOT PROVIDED. PLEASE NOTE THAT BASED ON TABLE |
| | 402.4(5) AND AN APPROXIMATE 125 TOTAL DEVELOPED LENGTH, |
| | A MINIMUM 1-INCH DIAMETER SCHEDULE 40 MAIN SUPPLY PIPE |
| | IS REQUIRED.) |
| | |
| | 2) FAILED. P0.1 & P0.2: REFER TO TABLE G2413.4(8) FBC |
| | RES- BASED ON THE PIPE LENGTHS SHOWN IT APPEARS THE |
| | 3/4-INCH PE BRANCH LINE SERVING THE POOL HEATER, |
| | GENERATOR AND GAS GRILL IS UNDERSIZED AND MUST BE |
| | INCREASED TO A MINIMUM 1-INCH PIPE. (THE PE PIPE HAS |
| | BEEN INCREASED TO 1-INCH PE, HOWEVER THE REVISED RISER |
| | DRAWING SHOWS THE FOLLOWING DEFICIENCIES:) |
| | |
| | A) THE LOW PRESSURE 1-INCH AND 1/2-INCH CSST ARE |
| | UNDERSIZED PER TABLE 402.4(15) WHICH IS PRINTED ON |
| | SHEET P0.1. BASED ON THE APPROX. 55 FT. TOTAL DEVELOPED |
| | LENGTH OF THE LOW PRESSURE RUN FROM THE REGULATOR TO |
| | THE GRILL AND TABLE 402.4(15) THE 1-INCH PIPE SHALL BE |
| | INCREASED TO 1-1/2-INCH AND THE 1/2-INCH SHALL BE |
| | INCREASED TO 1-1/4-INCH. |
| | |
| | B) PLEASE INDICATE THE TYPES AND SIZES OF PIPING FROM |
| | THE LOW PRESSURE REGULATOR TO THE GENERATOR AND TO THE |
| | POOL HEATER- SEC. 402.3 FBC FG. |
| | |
| | 3) FAILED. P0.1 & P0.2: PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALL MANUAL FOR THE NEW GAS |
| | GRILL- SEC. G2408.1 FBC RES. THE SPECS AND INSTALLATION |
| | INSTRUCTIONS HAVE BEEN SUBMITTED. REFER TO VENTILATION |
| | REQUIRMENTS IN THE MANUAL AND SHOW THE LOCATIONS AND |
| | SIZES OF UPPER AND LOWER VENTS REQUIRED FOR VENTILATION |
| | AND COMBUSTION AIR. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |