| Date |
Text |
| 2022-02-07 17:58:09 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 21120493 |
| | 2/7/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P0.1 & P0.2: BASED ON THE INCREASED 423,000 |
| | BTU LOAD PIPE SIZING FOR THE SYSTEM MUST BE |
| | RE-EVALUATED. PLEASE REFER TO SEC. G2412.3 & G2412.4 |
| | FBC RES, AND PROVIDE THE FOLLOWING INFORMATION: |
| | A) THE LENGTH OF THE BRANCH LINE TO THE GAS GRILL AND |
| | THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE OUTLET- SEC. G2413.4.1 FBC RES. |
| | B) THE SIZES AND LENGTHS OF THE SCHEDULE 40 METALLIC |
| | FROM THE METER TO THE PE- TABLE G2413.4(2) FBC RES. |
| | |
| | 2) P0.1 & P0.2: REFER TO TABLE G2413.4(8) FBC RES- |
| | BASED ON THE PIPE LENGTHS SHOWN IT APPEARS THE 3/4-INCH |
| | PE BRANCH LINE SERVING THE POOL HEATER, GENERATOR AND |
| | GAS GRILL IS UNDERSIZED AND MUST BE INCREASED TO A |
| | MINIMUM 1-INCH PIPE. |
| | |
| | 3) P0.1 & P0.2: PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALL MANUAL FOR THE NEW GAS |
| | GRILL- SEC. G2408.1 FBC RES. |
| | |
| | 4) P0.1 & P0.2: PLEASE NOTE A SEPARATE PERMIT IS |
| | REQUIRED OR INSTALLATION OF THE GENERATOR. A COMPLETE |
| | REVIEW IS NOT BEING PERFORMED AT THIS TIME. PLEASE BE |
| | ADVISED THAT THE UNIT SHALL BE LOCATED A MINIMUM OF 10 |
| | FT. AWAY FROM ANY MECHANCIAL OR GRAVITY AIR INTAKE |
| | OPENINGS INTO THE BUILDING- SEC. R303.5.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |