Plan Review Notes
Plan Review Notes For Permit 21120435
Permit Number 21120435
Review Stop B
Sequence Number 6
Notes
Date Text
2022-08-31 11:21:06BUILDING REVIEW APPROVED WITH PROVISO:
 NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION & INSPECTION TO AVOID CONFLICTS /DELAYS.
  
 1- DESIGN CRITERIA ON SHEET T-1: REVISE ROOF COMPONENTS
 & CLADDING DESIGN PRESSURES. TABLE R301.2(2) AND TABLE
 R301.2(3)FBC-RESIDENTIAL.
 2- PROVIDE COMPLETE DETAILS/SPECS FOR SECOND FLOOR WALL
 SEATING ON TOP OF EXISTING STRUCTURE. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS (TOP & BOTTOM),
 INTERIOR/EXTERIOR CONSTRUCTION, INSULATION, ETC.
 3- GLAZING IN BALCONY GUARDRAIL: PROVIDE SIGNED/SEALED
 ENGINEERING (SHOP DRAWINGS) FOR GLAZED RAILINGS. SHOP
 DRAWINGS (REVIEWED BY ARCHITECT OF RECORD BEFORE
 SUBMITTAL). IMPORTANT NOTE: TABLE R301.5
 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE
 "H"
 4- BUILDING THERMAL ENVELOPE. ARCHITECT OF RECORD NEEDS
 TO DEPICT THE BUILDING THERMAL ENVELOPE AND SPECIFY
 INSULATION MATERIALS AND THEIR R-VALUES.(ROOF, WALLS,
 RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY SEC.
 R103.2 FBC-ENERGY CONSERVATION.
 5- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE
 INSULATION SPECIFIED ON PLANS. NOTE: ARCHITECT TO
 REVIEW/APPROVE PRIOR TO SUBMITTAL.
 6- REVISE ENERGY CALCULATIONS: A)NEED BUILDER'S NAME.
 B)PLANS SUBMITTED SHOW GARAGE WITH A/C. REVISE
 CONDITIONED FLOOR AREA TO MATCH PLANS. C)REVISE R-VALUE
 OF FLOOR OVER GARAGE TO MATCH PLANS. D)WALL TYPES
 INFORMATION IS MISSING THE EXTERIOR FRAMED WALL ABOVE
 EXISTING CONCRETE BLOCK WALL. E)ATTIC IS DESIGNED AS
 UNVENTED. SEE PLANS AND REVISE AS REQUIRED. F)REVISE
 DOORS TYPE & SIZES TO MATCH PLANS. NOTE: GLAZED FRENCH
 DOORS NEED TO BE INCLUDED IN THE GLAZING AREA. G)REVISE
 WINDOW AREA AND WINDOW OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. H)REVISE ROOF TYPE INFORMATION TO MATCH
 PLANS. I)BUILDER TO COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
 7- DEFERRED PRODUCT APPROVAL:PROVIDE PRODUCT APPROVAL
 A) WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION
 SIZE).
 B) ARCHITECT TO REVIEW ABOVE PRODUCT APPROVALS
  
  