| 2022-05-26 14:26:53 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- DESIGN CRITERIA ON SHEET T-1: REVISE ROOF COMPONENTS |
| | & CLADDING DESIGN PRESSURES. TABLE R301.2(2) AND TABLE |
| | R301.2(3)FBC-RESIDENTIAL. |
| | |
| | 2- PROVIDE COMPLETE DETAILS/SPECS FOR SECOND FLOOR WALL |
| | SEATING ON TOP OF EXISTING STRUCTURE. SPECIFY ALL |
| | FRAMING MEMBERS AND CONNECTORS (TOP & BOTTOM), |
| | INTERIOR/EXTERIOR CONSTRUCTION, INSULATION, ETC. |
| | |
| | 3- GLAZING IN BALCONY GUARDRAIL: PROVIDE SIGNED/SEALED |
| | ENGINEERING (SHOP DRAWINGS) FOR GLAZED RAILINGS. SHOP |
| | DRAWINGS (REVIEWED BY ARCHITECT OF RECORD BEFORE |
| | SUBMITTAL). IMPORTANT NOTE: TABLE R301.5 |
| | FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE |
| | "H" |
| | |
| | 4- BUILDING THERMAL ENVELOPE. ARCHITECT OF RECORD NEEDS |
| | TO DEPICT THE BUILDING THERMAL ENVELOPE AND SPECIFY |
| | INSULATION MATERIALS AND THEIR R-VALUES.(ROOF, WALLS, |
| | RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY SEC. |
| | R103.2 FBC-ENERGY CONSERVATION. |
| | |
| | 5- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE |
| | INSULATION SPECIFIED ON PLANS. NOTE: ARCHITECT TO |
| | REVIEW/APPROVE PRIOR TO SUBMITTAL. |
| | |
| | 6- REVISE ENERGY CALCULATIONS: A)NEED BUILDER'S NAME. |
| | B)PLANS SUBMITTED SHOW GARAGE WITH A/C. REVISE |
| | CONDITIONED FLOOR AREA TO MATCH PLANS. C)REVISE R-VALUE |
| | OF FLOOR OVER GARAGE TO MATCH PLANS. D)WALL TYPES |
| | INFORMATION IS MISSING THE EXTERIOR FRAMED WALL ABOVE |
| | EXISTING CONCRETE BLOCK WALL. E)ATTIC IS DESIGNED AS |
| | UNVENTED. SEE PLANS AND REVISE AS REQUIRED. F)REVISE |
| | DOORS TYPE & SIZES TO MATCH PLANS. NOTE: GLAZED FRENCH |
| | DOORS NEED TO BE INCLUDED IN THE GLAZING AREA. G)REVISE |
| | WINDOW AREA AND WINDOW OVERHANG DEPTH AND SEPARATION TO |
| | MATCH PLANS. H)REVISE ROOF TYPE INFORMATION TO MATCH |
| | PLANS. I)BUILDER TO COMPLETE THE ENERGY PERFORMANCE |
| | LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | 7- DEFERRED PRODUCT APPROVAL:PROVIDE PRODUCT APPROVAL |
| | A) WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION |
| | SIZE). |
| | B) ARCHITECT TO REVIEW ABOVE PRODUCT APPROVALS |
| | |
| | |