2022-05-03 09:37:021ST REVIEW FMC
 PERMIT: 21120435
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS IS FOR 500 SQ FT AND FOR THE
 MASTER BATH ABOVE THE GARAGE. IF A MINI-SPLIT IS GOING
 TO BE INSTALLED IN THE GARAGE YOU MUST SUBMIT AN ENERGY
 CALCULATION SHOWING THE GARAGE SQ FT PLUS SHOWING THE
 GARAGE DOOR WITH THE WEATHER-STRIP. THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS HAS SHOWN THIS IN THE
 CALCULATIONS.
  
 2) PLEASE ADDRESS THE PREVIOUS COMMENTS LISTED BELOW.
  
 3) PLEASE SHOW THE DRYER EXHAUST DUCT MATERIAL AND THE
 TERMINATION LOCATION. FBC RES M1502
  
 4) PLEASE SHOW THE BATH EXHAUST FAN AND THE DUCT
 TERMINATION LOCATION. FBC RES M1507.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  