Plan Review Notes
Plan Review Notes For Permit 21120435
Permit Number 21120435
Review Stop B
Sequence Number 2
Notes
Date Text
2022-05-25 16:14:11RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21120435
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER
 OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT.
  
 1- OK
  
 ORIGINAL COMMENT:
 2-DESIGN CRITERIA ON SHEET T-1:
 B)REVISE ROOF COMPONENTS & CLADDING DESIGN PRESSURES.
 BASED ON HEIGHT OF BUILDING SHOWN ON EXTERIOR
 ELEVATIONS ON SHEET A-4, THE MULTIPLYING FACTOR TO USE
 FROM TABLE R301.2(3) IS 1.35 NOT 1.21. REVISE DESIGN
 PRESSURES AS REQUIRED. ALSO, WORST CASE SCENARIO IS FOR
 AN EFFECTIVE AREA OF 10PSF IN ROOF ZONE 3. REVISE
 DESIGN PRESSURES ACCORDINGLY.
 NOTE: PROPOSED ADDITION HAS A FLAT ROOF.
  
 RESPONSE:
 REVISE ROOF DESIGN PRESSURES. ROOF ZONE 3 IS THE WORST
 CASE AREA.
  
 ORIGINAL COMMENT:
 3- PLANS DON'T PROVIDE ANY INFORMATION FOR CONSTRUCTION
 OF NEW SECOND FLOOR WALL SEATING ON TOP OF EXISTING
 STRUCTURE. PROVIDE COMPLETE DETAILS AND SPECIFICATION
 FOR THIS WALL. PROVIDE COMPLETE WALL SECTION SHOWING
 THE LOAD PATH AS REQUIRED BY SEC. R601.2
 FBC-RESIDENTIAL.
  
 RESPONSE:
 NO INFORMATION WAS GIVEN FOR WALL CONSTRUCTION
 (INTERIOR/EXTERIOR, INSULATION, ETC.). NO STRUCTURAL
 CONNECTORS WERE SPECIFIED.
  
 4- OK.
 5- OK.
 6- OK.
 7- OK.
 8- OK.
  
 9- DEFERRED SUBMITTAL: SHEET A-4. GLAZING IN BALCONY
 GUARDRAIL:
 PROVIDE SIGNED/SEALED ENGINEERING (SHOP DRAWINGS) FOR
 GLAZED RAILINGS. SHOP DRAWINGS (REVIEWED BY ARCHITECT
 OF RECORD BEFORE SUBMITTAL). IMPORTANT NOTE: TABLE
 R301.5 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE
 NOTE "H"
 NOTE: THIS COULD BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. SPECIFY IN PLANS IF DEFERRED SUBMITTAL.
  
 10-OK.
  
 ORIGINAL COMMENT:
 11- BUILDING THERMAL ENVELOPE.
 A)ARCHITECT OF RECORD NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND
 THEIR R-VALUES.(ROOF, WALLS, RAISED FLOOR ABOVE GARAGE,
 ETC.) AS REQUIRED BY SEC. R103.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 NO R-VALUE INFORMATION GIVEN FOR EXTERIOR WALLS
 INSULATION (FRAMED AND MASONRY WALL) AND FOR ROOF.
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 12- DEFERRED SUBMITTAL: HOUSE IS DESIGNED WITH UNVENTED
 ATTIC. ARCHITECT IS SPECIFYING ICYNENE SPRAY
 INSULATION. PROVIDE ICC EVALUATION REPORT FOR THE
 ICYNENE INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 13- OK.
 14- OK.
  
 ORIGINAL COMMENT:
 15-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION. SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 C) PLANS SUBMITTED SHOW GARAGE WITH A/C. REVISE
 CONDITIONED FLOOR AREA TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)REVISE R-VALUE OF FLOOR OVER GARAGE TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)WALL TYPES INFORMATION ON PAGE ONE IS MISSING THE
 INFORMATION FOR EXTERIOR FRAMED WALL ABOVE EXISTING
 CONCRETE BLOCK WALL. COORDINATE WITH PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 F)ATTIC IS DESIGNED AS UNVENTED. SEE PLANS AND REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 G)REVISE DOORS INFORMATION TO MATCH PLANS AND PRODUCT
 APPROVALS SUBMITTED.
 REVISE DOOR TYPE AND SIZES. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
 NOTE: GLAZED FRENCH DOORS NEED TO BE INCLUDED IN THE
 GLAZING AREA. REVISE AS REQUIRED.
  
 H)REVISE WINDOWS INFORMATION TO MATCH PLANS AND PRODUCT
 APPROVALS SUBMITTED. REVISE WINDOW AREA AND WINDOW
 OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 I)REVISE ROOF TYPE INFORMATION TO MATCH PLANS AND
 PRODUCT APPROVALS SUBMITTED. FBC- ENERGY CONSERVATION.
 THIS IS A FLAT ROOF NOT PITCH
  
 J)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
  
 16- DEFERRED PRODUCT APPROVAL:PROVIDE PRODUCT APPROVAL
 AS REQUIRED BY FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY DOOR.
  
 B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
  
 17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS,
 INCLUDING THE ONES ALREADY SUBMITTED AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH PRODUCT APPROVAL LIST ON SHEET
 T-1. MAKE SURE ALL PRODUCT APPROVALS ARE LISTED AND
 NOA'S ARE CORRECT.
  
 18- WIND RESISTANCE OF EXTERIOR SOFFITS: TYPICAL WALL
 SECTIONS ONLY SPECIFY "7/8" STUCCO O/ MTL. LATH W/
 SMOOTH SAND FINISH". ARCHITECT OF RECORD TO PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE SOFFIT
 CONSTRUCTION SHOWING COMPLIANCE WITH SEC. R704
 FBC-RESIDENTIAL. NOTE: PROVIDE SPECIFICATIONS SHOWING
 COMPLIANCE WITH ASTM C1063 (SEE TABLE 3 OF ASTM C1063).
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,