| 2022-05-25 16:14:11 | RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21120435 |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | ***IMPORTANT*** |
| | ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER |
| | OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT. |
| | |
| | 1- OK |
| | |
| | ORIGINAL COMMENT: |
| | 2-DESIGN CRITERIA ON SHEET T-1: |
| | B)REVISE ROOF COMPONENTS & CLADDING DESIGN PRESSURES. |
| | BASED ON HEIGHT OF BUILDING SHOWN ON EXTERIOR |
| | ELEVATIONS ON SHEET A-4, THE MULTIPLYING FACTOR TO USE |
| | FROM TABLE R301.2(3) IS 1.35 NOT 1.21. REVISE DESIGN |
| | PRESSURES AS REQUIRED. ALSO, WORST CASE SCENARIO IS FOR |
| | AN EFFECTIVE AREA OF 10PSF IN ROOF ZONE 3. REVISE |
| | DESIGN PRESSURES ACCORDINGLY. |
| | NOTE: PROPOSED ADDITION HAS A FLAT ROOF. |
| | |
| | RESPONSE: |
| | REVISE ROOF DESIGN PRESSURES. ROOF ZONE 3 IS THE WORST |
| | CASE AREA. |
| | |
| | ORIGINAL COMMENT: |
| | 3- PLANS DON'T PROVIDE ANY INFORMATION FOR CONSTRUCTION |
| | OF NEW SECOND FLOOR WALL SEATING ON TOP OF EXISTING |
| | STRUCTURE. PROVIDE COMPLETE DETAILS AND SPECIFICATION |
| | FOR THIS WALL. PROVIDE COMPLETE WALL SECTION SHOWING |
| | THE LOAD PATH AS REQUIRED BY SEC. R601.2 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | NO INFORMATION WAS GIVEN FOR WALL CONSTRUCTION |
| | (INTERIOR/EXTERIOR, INSULATION, ETC.). NO STRUCTURAL |
| | CONNECTORS WERE SPECIFIED. |
| | |
| | 4- OK. |
| | 5- OK. |
| | 6- OK. |
| | 7- OK. |
| | 8- OK. |
| | |
| | 9- DEFERRED SUBMITTAL: SHEET A-4. GLAZING IN BALCONY |
| | GUARDRAIL: |
| | PROVIDE SIGNED/SEALED ENGINEERING (SHOP DRAWINGS) FOR |
| | GLAZED RAILINGS. SHOP DRAWINGS (REVIEWED BY ARCHITECT |
| | OF RECORD BEFORE SUBMITTAL). IMPORTANT NOTE: TABLE |
| | R301.5 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE |
| | NOTE "H" |
| | NOTE: THIS COULD BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. SPECIFY IN PLANS IF DEFERRED SUBMITTAL. |
| | |
| | 10-OK. |
| | |
| | ORIGINAL COMMENT: |
| | 11- BUILDING THERMAL ENVELOPE. |
| | A)ARCHITECT OF RECORD NEEDS TO DEPICT THE BUILDING |
| | THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND |
| | THEIR R-VALUES.(ROOF, WALLS, RAISED FLOOR ABOVE GARAGE, |
| | ETC.) AS REQUIRED BY SEC. R103.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | RESPONSE: |
| | NO R-VALUE INFORMATION GIVEN FOR EXTERIOR WALLS |
| | INSULATION (FRAMED AND MASONRY WALL) AND FOR ROOF. |
| | NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 12- DEFERRED SUBMITTAL: HOUSE IS DESIGNED WITH UNVENTED |
| | ATTIC. ARCHITECT IS SPECIFYING ICYNENE SPRAY |
| | INSULATION. PROVIDE ICC EVALUATION REPORT FOR THE |
| | ICYNENE INSULATION TO VERIFY COMPLIANCE WITH SEC. R316 |
| | FBC-RESIDENTIAL. |
| | NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN |
| | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 13- OK. |
| | 14- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 15-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106 |
| | FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY |
| | CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | RESPONSE: |
| | A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED |
| | AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY |
| | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| | REQUIRED BY SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| | RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION. SECTION R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC- |
| | ENERGY CONSERVATION. |
| | |
| | C) PLANS SUBMITTED SHOW GARAGE WITH A/C. REVISE |
| | CONDITIONED FLOOR AREA TO MATCH PLANS. SEC. |
| | R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| | |
| | D)REVISE R-VALUE OF FLOOR OVER GARAGE TO MATCH PLANS. |
| | SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| | |
| | E)WALL TYPES INFORMATION ON PAGE ONE IS MISSING THE |
| | INFORMATION FOR EXTERIOR FRAMED WALL ABOVE EXISTING |
| | CONCRETE BLOCK WALL. COORDINATE WITH PLANS. |
| | SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| | |
| | F)ATTIC IS DESIGNED AS UNVENTED. SEE PLANS AND REVISE |
| | AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | G)REVISE DOORS INFORMATION TO MATCH PLANS AND PRODUCT |
| | APPROVALS SUBMITTED. |
| | REVISE DOOR TYPE AND SIZES. SEC. R101.5.1.1.2 FBC- |
| | ENERGY CONSERVATION. |
| | NOTE: GLAZED FRENCH DOORS NEED TO BE INCLUDED IN THE |
| | GLAZING AREA. REVISE AS REQUIRED. |
| | |
| | H)REVISE WINDOWS INFORMATION TO MATCH PLANS AND PRODUCT |
| | APPROVALS SUBMITTED. REVISE WINDOW AREA AND WINDOW |
| | OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC. |
| | R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| | |
| | I)REVISE ROOF TYPE INFORMATION TO MATCH PLANS AND |
| | PRODUCT APPROVALS SUBMITTED. FBC- ENERGY CONSERVATION. |
| | THIS IS A FLAT ROOF NOT PITCH |
| | |
| | J)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | |
| | 16- DEFERRED PRODUCT APPROVAL:PROVIDE PRODUCT APPROVAL |
| | AS REQUIRED BY FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)ENTRY DOOR. |
| | |
| | B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO AVOID DELAYS/CONFLICTS). |
| | |
| | 17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS, |
| | INCLUDING THE ONES ALREADY SUBMITTED AS REQUIRED BY |
| | SEC. 107.3.4.1 CITY AMENDMENTS. |
| | NOTE: COORDINATE WITH PRODUCT APPROVAL LIST ON SHEET |
| | T-1. MAKE SURE ALL PRODUCT APPROVALS ARE LISTED AND |
| | NOA'S ARE CORRECT. |
| | |
| | 18- WIND RESISTANCE OF EXTERIOR SOFFITS: TYPICAL WALL |
| | SECTIONS ONLY SPECIFY "7/8" STUCCO O/ MTL. LATH W/ |
| | SMOOTH SAND FINISH". ARCHITECT OF RECORD TO PROVIDE |
| | COMPLETE DETAILS AND SPECIFICATIONS FOR THE SOFFIT |
| | CONSTRUCTION SHOWING COMPLIANCE WITH SEC. R704 |
| | FBC-RESIDENTIAL. NOTE: PROVIDE SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH ASTM C1063 (SEE TABLE 3 OF ASTM C1063). |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |