2022-03-28 18:00:59RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21120435
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT
 OF RECORD. ALL DRAWINGS NEED TO BE SIGNED AND SEALED AS
 REQUIRED BY CHAPTER 481 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH ARCHITECT'S
 DIGITAL SIGNATURE OR PROVIDE HARD COPY PLANS WITH
 ARCHITECT'S ORIGINAL SEAL AND SIGNATURE.
  
 2-DESIGN CRITERIA ON SHEET T-1:
 A)REVISE WALLS COMPONENTS & CLADDING DESIGN PRESSURES.
 BASED ON HEIGHT OF BUILDING SHOWN ON EXTERIOR
 ELEVATIONS ON SHEET A-4, THE MULTIPLYING FACTOR TO USE
 FROM TABLE R301.2(3) IS 1.35 NOT 1.21. REVISE DESIGN
 PRESSURES AS REQUIRED. ALSO, WORST CASE SCENARIO IS FOR
 AN EFFECTIVE AREA OF 10PSF IN AN END ZONE. REVISE
 DESIGN PRESSURES ACCORDINGLY.
  
 B)REVISE ROOF COMPONENTS & CLADDING DESIGN PRESSURES.
 BASED ON HEIGHT OF BUILDING SHOWN ON EXTERIOR
 ELEVATIONS ON SHEET A-4, THE MULTIPLYING FACTOR TO USE
 FROM TABLE R301.2(3) IS 1.35 NOT 1.21. REVISE DESIGN
 PRESSURES AS REQUIRED. ALSO, WORST CASE SCENARIO IS FOR
 AN EFFECTIVE AREA OF 10PSF IN ROOF ZONE 3. REVISE
 DESIGN PRESSURES ACCORDINGLY.
 NOTE: PROPOSED ADDITION HAS A FLAT ROOF.
  
 C)REVISE BUILDING DESIGN PRESSURES SPECIFIED UNDER THE
 PRODUCT APPROVAL SUBMITTAL AFFIDAVIT LIST SHOWN ON
 SHEET T-1. COORDINATE WITH ITEM #2(A) ABOVE AND REVISE
 AS REQUIRED.
  
 D)DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD LOADS
 FOR SECOND FLOOR, CANTILEVERED BALCONY AND SECOND FLOOR
 ROOF. CLEARLY SPECIFY SECOND FLOOR LIVE AND DEAD LOADS
 (TOP AND BOTTOM CHORDS) AND ROOF LIVE AND DEAD LOADS.
 SEC. R301.4 FBC-RESIDENTIAL.
 SEC. R301.5 FBC-RESIDENTIAL AND TABLE R301.5
 FBC-RESIDENTIAL.
  
 3- PLANS DON'T PROVIDE ANY INFORMATION FOR CONSTRUCTION
 OF NEW SECOND FLOOR WALL SEATING ON TOP OF EXISTING
 STRUCTURE. PROVIDE COMPLETE DETAILS AND SPECIFICATION
 FOR THIS WALL. PROVIDE COMPLETE WALL SECTION SHOWING
 THE LOAD PATH AS REQUIRED BY SEC. R601.2
 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY CONSTRUCTION. PROVIDE DIMENSIONS, FRAMING
 INFORMATION, HANDRAIL SPECS, RISER AND TREAD SPECS,
 FIREBLOCKING, ETC. SHOWING COMPLIANCE WITH ALL THE
 REQUIREMENTS OF SEC. R311.7 FBC-RESIDENTIAL.
  
 5- SHEET D-1:
 A)FOUNDATION PLAN DOESN'T PROVIDE ANY INFORMATION FOR
 ATTACHMENT OF NEW FOOTING TO EXISTING STRUCTURE. SEC.
 107.2.1 CITY AMENDMENTS. SEC. R401.2 FBC-RESIDENTIAL,
 SEC. R601.2 FBC-RESIDENTIAL.
  
 B)FOOTING SIZE SPECIFIED ON WALLS SECTIONS ON SHEET
 A-3(DETAILS) DON'T MATCH FOOTING SIZE SPECIFIED ON
 FOUNDATION PLAN. REVISE AS REQUIRED TO MATCH. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 6- GARAGE FIRE RESISTANCE CONSTRUCTION:
 A) PROVIDE FIRE RATING SPECIFICATIONS FOR THE SWING
 DOOR LEADING FROM THE NEW GARAGE TO THE MAIN HOUSE AS
 REQUIRED BY SEC. R302. 5.1 FBC-RESIDENTIAL.
  
 B)PROVIDE SPECIFICATIONS FOR CEILING DWELLING-GARAGE
 SEPARATION SHOWING COMPLIANCE WITH SEC. R302.6
 FBC-RESIDENTIAL AND TABLE R302.6 FBC-RESIDENTIAL.
  
 7- BALCONY INFORMATION ON SECOND FLOOR PLAN ON SHEET
 A-1 IS INCOMPLETE. IT DOESN'T SHOW ANY GUARDRAIL.
 PROVIDE COMPLETE INFORMATION AND SPECIFICATIONS. SEC.
 R312.1 FBC-RESIDENTIAL.
  
 8-SHEET A-3(ROOF PLAN):
 A)PROVIDE COMPLETE FRAMING PLAN FOR PROPOSED BALCONY.
 SPECIFY ALL FRAMING MEMBERS TYPE, SIZE AND SPACING.
 SPECIFY FASTENING AT THE END OF EACH STRUCTURAL MEMBER.
 SPECIFY BALCONY DECKING AND FASTENING SPECIFICATIONS.
 CLARIFY SUPPORT OF CANTILEVERED BALCONY. SEC. R301.1
 FBC-RESIDENTIAL AND SEC. R301.2.1 FBC-RESIDENTIAL.
  
 B)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 ATTACHMENT SECOND FLOOR TRUSSES TO NEW WALL SEATING ON
 EXISTING WALL. SEC. R301.1 FBC-RESIDENTIAL.
  
 C) COORDINATE STRUCTURAL LEDGER SPECIFICATIONS
 SPECIFIED ON THE SECOND FLOOR FRAMING PLAN WITH LEDGER
 SPECIFICATIONS SHOWN ON WALL SECTION DETAIL ON SHEET
 A-3 (DETAILS). NEED TO SPECIFY HOW MUCH EMBEDMENT IS
 REQUIRED FOR THE 5/8" WEDGE ANCHORS AND NEED TO
 COORDINATE ANCHOR SPACING TO MATCH. CHECK SECOND FLOOR
 LOADS DESIGN WHEN SPECIFYING THE ANCHOR SPACING.
 NOTE: THERE ARE TWO A-3 SHEETS SUBMITTED. A-3(ROOF
 PLAN) AND A-3(DETAILS). REVISE S REQUIRED TO AVOID
 CONFLICTS.
  
 9- SHEET A-4. GLAZING IN BALCONY GUARDRAIL:
 A)PROVIDE SIGNED/SEALED ENGINEERING (SHOP DRAWINGS) FOR
 GLAZED RAILINGS. SHOP DRAWINGS (REVIEWED BY ARCHITECT
 OF RECORD BEFORE SUBMITTAL). IMPORTANT NOTE: TABLE
 R301.5 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE
 NOTE "H"
 NOTE: THIS COULD BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. SPECIFY IN PLANS IF DEFERRED SUBMITTAL.
  
 B)REAR ELEVATION IS INCOMPLETE. SEE PLANS AND REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 10-SHEET A-3(DETAILS):
 A) REVISE ROOF ZONE DETAIL. SEE FIGURE R301.2(7) OF
 CURRENT 2020 RESIDENTIAL CODE FOR NEW ROOF ZONES
 DESIGNATIONS AND REVISE AS REQUIRED.
 NOTE: PROPOSED ROOF IS A FLAT ROOF.
  
 B)THERE ARE TWO DIFFERENT ROOF SHEATHING SPECIFICATIONS
 ON THIS SHEET.
 NEED TO PROVIDE ONLY ONE TO AVOID CONFLICTS/DELAYS.
 REVISE AS REQUIRED. NOTE: NEED TO USE RING SHANK NAILS
 AND ROOF SHEATHING NEEDS TO BE NAILED WITH AT 4 INCHES
 O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC.
 R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
  
 11- BUILDING THERMAL ENVELOPE.
 A)ARCHITECT OF RECORD NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND
 THEIR R-VALUES.(ROOF, WALLS, RAISED FLOOR ABOVE GARAGE,
 ETC.) AS REQUIRED BY SEC. R103.2 FBC-ENERGY
 CONSERVATION.
  
 12-HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING ICYNENE SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE ICYNENE INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 13- ARCHITECT NEEDS TO SPECIFY CARBON MONOXIDE ALARM
 WITHIN ALL SLEEPING ROOMS, INCLUDING EXISTING BEDROOMS
 AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 14-PROVIDE COMPLETE STRUCTURAL BUCK DETAIL AND
 FASTENING SPECIFICATIONS FOR NEW OVERHEAD GARAGE DOOR.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 15-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 16- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)INSWING FRENCH DOORS AS SHOWN ON PLANS.
  
 B)ENTRY DOOR.
  
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
  
 17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS,
 INCLUDING THE ONES ALREADY SUBMITTED AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH PRODUCT APPROVAL LIST ON SHEET
 T-1. MAKE SURE ALL PRODUCT APPROVALS ARE LISTED AND
 NOA'S ARE CORRECT.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION