| 2022-08-03 13:50:01 | THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN |
| | DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH |
| | FIRE RESCUE. |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THE LETTER FROM JEFFREY P. COLLINS, MS, PE HAS BEEN |
| | RECEIVED AND ACCEPTED BY THE DIVISION OF FIRE |
| | PREVENTION AS ACCEPTABLE IN ADDRESSING THE LIFE SAFETY |
| | CONCERNS REGARDING CHANGE OF USE TO AN EDUCATIONAL |
| | OCCUPANCY, SPECIFICALLY REGARDING THE FOLLOWING ITEMS: |
| | |
| | 5. PROVIDE FIRE DEPARTMENT ACCESS TO THE AREAS THAT ARE |
| | BLOCKED OFF. THE WON DOORS CLOSING OFF THE STAIRWELLS |
| | WILL NEED TO BE ACCESSIBLE FOR MEANS OF EGRESS FROM THE |
| | STAIRWELL. KEYS FOR ENTRY MUST BE PROVIDED TO THE FIRE |
| | DEPARTMENT. |
| | 6. FIRE EXTINGUISHER PLACEMENT SHOWN ON REVISED LS2.0. |
| | 8. A DOOR SCHEDULE WITH HARDWARE IS REQUIRED. EXISTING |
| | DOORS PROVIDED IN SEPARATE DOCUMENT. |
| | |
| | TRAVEL DISTANCE COMPLIES WITH THE LIFE SAFETY CODE, |
| | NFPA 101 (FFPC.) THE SPRINKLER SYSTEM FOR THE ENTIRE |
| | BUILDING MUST BE FULLY OPERATIONAL. THE FIRE ALARM MUST |
| | ALSO BE FULLY OPERATIONAL. |
| | -SPRINKLER AND FIRE ALARM SYSTEMS REQUIRE SERVICE |
| | TESTING BY APPROPRIATE LICENSED/CERTIFIED |
| | CONTRACTOR(S). |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION PRIOR TO OCCUPANCY. |
| | FAILURE TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN |
| | A FAILED FIRE INSPECTION. |
| | |
| | |
| | PER CITY CODES, SITE IS SUBJECT TO FIELD INSPECTIONS, |
| | REQUIRED TESTING AND APPROVAL PRIOR TO OCCUPANCY IN NEW |
| | CLASSIFICATION. |
| | |
| | LT. BRIAN DOLAN |
| | DIVISION OF FIRE PREVENTION |
| | 561-804-4752 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |