| 2022-07-12 16:39:28 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | FBC B 107.2.1, PROVIDE MORE DETAILED INFORMATION. |
| | |
| | CONSIDERING SECTIONS 1012.5.2 & 1012.6.2 OF THE FBC EB |
| | THE EXISTING HEIGHT/AREA & WALL RATINGS HAVE BEEN MET. |
| | HOWEVER, AS PER FBC EB 1012.4.2, THE MEANS OF EGRESS |
| | DETAILS FROM FBC B CHAPTER 10 MUST BE IDENTIFIED. |
| | |
| | 1.) IDENTIFY THE PANIC HARDWARE ON EGRESS DOORS AS PER |
| | SCTION FBC B 1010.1.10. |
| | 2.) FBC B 107.2.1, INDICATE HOW THE ACCESS TO STAIRS AT |
| | 1ST FLOOR WILL BE CLOSED OFF. |
| | 3.) FBC B 107.2.1, PROVIDE A SIGNED LETTER FROM OWNER |
| | AND DESIGNER OF RECORD AS TO HOW AND WHY THE TOTAL |
| | OCCUPANT # IS AT 159 OCCUPANTS. CONSIDERING THE |
| | EDUCATION OCCUPANCY AND FBC B TABLE 1004.5 WE NEED TO |
| | BE SURE THAT WE WILL NOT HAVE AN OCCUPANCY ISSUE. FOR |
| | EXAMPLE, A CONFLICT WITH THE FUTURE NUMBER OF OCCUPANTS |
| | AND THE BATHROOM CAPACITY. |
| | 4.) FBC B 468.3.5.2, INDICATE THE LOCATION OF STAFF |
| | BATHROOMS AND SEPARATE STUDENT BATHROOMS. |
| | 5.) FBC B 468.3.7, INDICATE HOW THE LIGHTING IS SET UP |
| | TO MEET THE CODE REQUIREMENTS. AS THE EXISTING LIGHTING |
| | FROM THE LATS OCCUPANCY (RESTAURANT) MAY NOT BE |
| | SUFFICIENT. |
| | |