| Plan Review Notes For Permit 21120324 |
| Permit Number |
21120324 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-10 13:03:50 | PLEASE SEE THE FIRE REVIEWERS COMMENTS BELOW: | | | | | | | | | NFPA 96 | | | | | | 10.2.2* A PLACARD SHALL BE CONSPICUOUSLY PLACED NEAR | | | EACH EXTINGUISHER THAT STATES THAT THE FIRE PROTECTION | | | SYSTEM SHALL BE ACTIVATED PRIOR TO USING THE FIRE | | | EXTINGUISHER. | | | 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION | | | SHALL BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. | | | AND 48 IN.)ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT | | | OF A FIRE, BE LOCATEDIN A PATH OF EGRESS, AND CLEARLY | | | IDENTIFY THE HAZARD PROTECTED. INDICATE MOUNTING HEIGHT | | | AND LOCATION. | | | 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE | | | LOCATED A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M | | | (20 FT) FROM THE PROTECTED HOOD EXHAUST SYSTEM(S) | | | WITHIN A PATH OF EGRESS | | | OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE AHJ. | | | INDICATE LOCATION ON A FLOOR PLAN. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|