2022-03-17 09:33:53ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL ON DRAWING COMPLIANCE WITH THE
 FOLLOWING NEC REQUIREMENTS:
 A) NEC 210.8 GFCI PROTECTION
 B) NEC 210.12 AND NEC 406.4 ARC-FAULT PROTECTION
 C) NEC 220.52 RECEPTACLE SPACING
 D) NEC 406.12 AND NEC 406.4(D)(5) TAMPER RESISTANT
 RECEPTACLES
 E) NEC 250.140 RANGE GROUNDING
 F) SMOKE/CARBON ALARMS AS PER FBC 553.883
 G) PLEASE PROVIDE SPECIFICATIONS OF NEW LIGHTS. THEY
 ARE STATED AS LOW VOLTAGE. WILL THIS BE LOW VOLTAGE
 WIRING? WHERE WILL THE LED DRIVER BE LOCATED? IF LOW
 VOLTAGE WIRING, PLEASE DETAIL WIRE TYPE AND INDICATE
 WHETHER CEILING IS A PLENUM
 2) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR OR
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
 3) PLEASE HAVE THE CONTRACTOR OR QUALIFIER WHO PREPARED
 THE DRAWING PROVIDE HIS/HER SIGNATURE ON IT- SECTION
 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) &
 471.025.
  
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved