2022-02-25 10:25:13BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 21120322
 REVIEWED: JANUARY 31, 2022
 2ND REVIEW FEBRUARY 25, 2022
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2020)
 FBC[AMENDED] = 2020 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1. RESOLVED
  
 2. TYPE OF CEILING ASSEMBLE INCLUDING THICKNESS OF
 CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT
 BELOW.
  
 3. PROVIDE REPORTS FOR SOUND TRANSMISSION( AND FLAME
 SPREAD (3 TOTAL)
 THE PROCORE PLUS DATA SHEET PROVIDES NO INFO ON THE
 SOUND TRANSMISSION.
 HOW ARE YOU ACHIEVING IIC OF 50 AND STC 50?
 IF THERE IS ANOTHER UNDERLAYMENT PLEASE PROVIDE SOUND
 REPORTS FOR IIC AND STC, OR PROVIDE REPORTS TO SHOW
 PROCORE MEETS SOUND TRANSMISSION..
  
 4. RESOLVED
  
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
  
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
  
 603.1 FBC[B] ALLOWABLE MATERIALS IN NON-COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
  
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR
 COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2
 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND
 COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL,
 LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING
 MATERIALS THAT ARE NOT COMPRISED OF FIBERS.
  
 NOTES:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  