| Plan Review Notes For Permit 21120322 |
| Permit Number |
21120322 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-14 07:53:19 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L. | | | FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING | | | COMMENTS: | | | | | | 1) THE APPLICATION INDICATES THERE WILL BE THE | | | REPLACEMENT OF FLOORING AND CABINETS BUT NO DOCUMENTS | | | IDENTIFIYING WHAT MATERIALS ARE BEING USED. | | | | | | 2) WITH THE DOCUMENTS IDENTIFYING MATERIALS BEING USED, | | | PLEASE PROVIDE THE PRODUCT SPECS FOR ALL MATERIALS | | | (FLOORING, UNDERLAYMENT, CABINETS) | | | | | | PER NFPA 101 CHAPTER 10, 10.2.7.2 | | | | | | SHALL MEET THE MINIMUM CRITICAL RADIENT FLUX. | | | | | | CAITLIN L. FRANCIS | | | FIRE INVESTIGATOR | | | 561-804-4728 | | | [email protected] | | | | | | |
|