| 2022-01-31 11:29:55 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 21120322 |
| | REVIEWED: JANUARY 31, 2022 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2020) |
| | FBC[AMENDED] = 2020 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1. FLOOR PLAN LAYOUT TO SHOW AREA AND TYPE OF FLOORING |
| | FOR EACH AREA. |
| | |
| | 2. TYPE OF CEILING ASSEMBLE INCLUDING THICKNESS OF |
| | CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT |
| | BELOW. |
| | |
| | 3. PROVIDE REPORTS FOR SOUND TRANSMISSION( AND FLAME |
| | SPREAD (3 TOTAL) |
| | |
| | 4. PROVIDE PLAN FOR DEMO, PLUMBING AND ELECTRICAL |
| | |
| | 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND |
| | SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF |
| | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E90. |
| | |
| | 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR |
| | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR |
| | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E492. |
| | |
| | 603.1 FBC[B] ALLOWABLE MATERIALS IN NON-COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR |
| | COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2 |
| | THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND |
| | COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL, |
| | LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING |
| | MATERIALS THAT ARE NOT COMPRISED OF FIBERS. |
| | |
| | NOTES: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |