| 2022-02-03 14:08:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS NO CLEAR INDICATION OF THE TYPE OF |
| | REPLACEMENT FLOOR TILE. |
| | |
| | THERE IS AN INDICATION OF THE SPEC SHEET FOR THE FLOOR |
| | UNDERLAYMENT, BUT NO SPEC SHEET FOR THE ACTUAL PROPOSED |
| | FLOORING TILE. |
| | |
| | TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT |
| | CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE A |
| | VINYL/LAMINATE TYPE AND CAN BE MANUFACTURED FROM AROUND |
| | THE WORLD AND NOT ALL ARE TESTED AND MEETING LISTED AND |
| | NFPA STANDARDS. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC |
| | TILE TYPE AND/OR PRODUCT SPEC SHEET ( IF A |
| | VINYL/LAMINATE TYPE, INDICATING THE INTERIOR FINISH |
| | CLASS RATING OR FIRE BEHAVIOR RATING). |
| | |
| | |
| | 2) THE PROPOSED DEMO INDICATES THE REMOVAL OF WALLS. |
| | |
| | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS MAY AFFECT |
| | FIRE/SMOKE ALARM DEVICES |
| | |
| | ANY FIRE/SMOKE ALARM DEVICES SHALL BE |
| | MAINTAINED/REPLACED IF AFFECTED. |
| | |
| | FIRE ALARM WORK, INCLUDING DEMO, SHALL BE UNDER |
| | SEPARATE PERMIT & SHOP DRAWINGS, BY A FA CONTRACTOR. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |