Plan Review Notes
Plan Review Notes For Permit 21120311
Permit Number 21120311
Review Stop G
Sequence Number 1
Notes
Date Text
2021-12-17 11:12:1012/17/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SHOW ON THE ISOMETRIC DRAWING THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
  
 2. WOULD YOU PLEASE SHOW THE CORRESPONDING EHD NUMBER
 OF THE CORRUGATED STAINLESS STEEL TUBING PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THE TANKLESS UNIT CALL FOR A 10.5" WATER COLUMN, AND
 THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 5. THE CSST PIPE SAYS 50 FT, AND THE LONGEST RUN IS
 ALSO 50 FT. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE
 POINT OF DELIVERY (GAS METER / MP REGULATOR / LP TANK)
 TO THE MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM
 PER THE 2020 FBC RES. SEC. G2413.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR (CLOTHES
 DRYERS AND RANGE) PER THE 2020 FBC RES. SEC. G2407.1
 AND G2439.4. IF USING LOUVERS, HOW THE LOCATION THAT IS
 BEING INSTALLED FOR THE COMBUSTION AIR. THE LOUVERS
 CANNOT BE LOCATED ON AN EXTERIOR WALL THAT IS FIRE
 RATED AS THE FIRE RATING OF THE WALL MUST BE MAINTAINED
 PER THE WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 7. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT
 OF REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES.
 SEC G2421.2.
  
 8. WOULD YOU PLEASE LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020 FBC
 RES. SEC. G2420.5.
  
 9. DRIP LEG IS MISSING ON TANKLESS PER THE 2020 FBC
 RES. SEC. G2419.2.
  
 10. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 11. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3. WOULD YOU PLEASE NOTE ON PLANS?
  
 12. CONDENSATE FOR TANKLESS NEEDS TO BE 1' AWAY FROM
 THE STRUCTURE PER THE 2020 FBC SEC. R318.5.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 NOTE THE 2020 IS NOT USED SE USE THE WEST PALM BEACH
 AMENDMENTS 2017 FBC CHAPTER.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  