| 2022-08-01 13:31:10 | INSUFFICIENT | | | | | | 1) REPEAT COMMENT: THE LOCATION OF THE HANDHOLE AND THE | | | INSTALL EXCAVATION SHOWN ADJACENT TO THE POLE SUPPLYING | | | POWER WILL DAMAGE THE ROOT SYSTEM OF THE EXISTING LARGE | | | STREET TREE IF INSTALLED IN THE LOCATION SHOWN ON SHEET | | | P-1. THE HANDHOLE MAY NOT BE INSTALLED AT THIS | | | LOCATION. *** THE EXCAVATION PIT CONTINUES TO BE SHOWN | | | LESS THEN 5 FEET FROM THE TREE, WHICH IS TOO CLOSE. IT | | | NEEDS TO BE AT LEAST 10 FEET AWAY, ESPECIALLY GIVEN THE | | | SIZE OF THE TREE. STAFF SUGGESTS THAT THE HANDHOLE BE | | | INSTALLED UNDER THE SIDEWALK SO THAT IT, AND THE | | | EXCAVATION, ARE FURTHER AWAY FROM THE TREE AND IN AN | | | AREA THAT TYPICALLY SEES LESS ROOT ZONE EXPANSION. | | | | | | 2) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. | | | THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP | | | 7042 TRAFFIC GREY A. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|