| 2023-02-24 15:04:40 | 1. CONCRETE CAISSON IS SHOWN ON SURVEY TO CONFLICT WITH | | | EXISTING GAS LINE, PLEASE PROVIDE THE NECESSARY PUBLIC | | | UTILITY LETTER GRANTING APPROVAL OF THIS PROPOSED POLE | | | LOCATION AND DEPTH. | | | | | | 2. PROPOSED BORE PITS AND HANDHOLE APPEAR TO BE TOO | | | CLOSE TO EXISTING PALM TREES, PLEASE PROVIDE DIMENSION | | | OF CLEARANCE BETWEEN EXCAVATION WORK AND TREES. | | | RECOMMENDED AT LEAST 5 FT. CLEARANCE FROM PALMS TO | | | SAFELY PROVIDE A BUFFER TO THE ROOT SYSTEM. | | | | | | 4. THE POLE STEALTH DESIGN, HEIGHT, AND COLOR MEETS | | | CITY STANDARDS. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | (561)822-1426 | | | [email protected] | | | |
|