| 2022-01-31 17:55:31 | FAILED |
| | |
| | 1) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. |
| | |
| | 2) PLEASE RELOCATE THE POLE IN LINE WITH THE EXISTING |
| | STREETLIGHT POLE (CLOSER TO THE CURB). THIS WILL PERMIT |
| | THE INSTALLATION OF A FULL WIDTH SIDEWALK THAT IS NOT |
| | OBSTRUCTED BY THE POLE AT SUCH TIME THAT THE ADJACENT |
| | PROPERTY IS DEVELOPED. |
| | . |
| | 3) THE POLE HEIGHT SHOWN ON SHEET C-3 LISTS THE HEIGHT |
| | TO THE TOP OF THE ANTENNA AS 28 FEET ABOVE GRADE; |
| | HOWEVER, THE SITE PLAN AND SURVEY CALL OUT A POLE 32 |
| | FEET ABOVE GRADE LEVEL. ALL SHEETS MUST SHOW |
| | CONSISTENT, ACCURATE INFORMATION. NOTE: THE 32-FOOT |
| | HEIGHT IS CONSISTENT WITH ONE OF THE NEARBY POWER |
| | POLES. |
| | |
| | 4) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE |
| | THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE |
| | IN LANDSCAPED AREAS AND NOT OVERLAPPING WITH A |
| | SIDEWALK. PLEASE UPDATE THE NOTATIONS ACCORDINGLY. |
| | |
| | 5) THE PLANS SHOW THE BORE PITS BEING DUG WITH AN |
| | UNDERGROUND ELECTRIC LINE RUNNING THROUGH THEM AND THE |
| | HANDHOLE INSTALLED ON TOP OF A COMCAST LINE. IN ORDER |
| | TO VERIFY THAT THE INSTALLATION WILL NOT INTERFERE WITH |
| | THE EXISTING FACILITIES, PROVIDE A PUBLIC UTILITY |
| | LETTER OF NO OBJECTION FROM FPL AND COMCAST REGARDING |
| | THE INSTALLATION. |
| | |
| | 6) PROVIDE CROSS SECTIONS OF THE UNDERGROUND ELECTRIC |
| | BORE FOR THE FULL LENGTH OF THE INSTALLATION. THE |
| | UNDERGROUND ELECTRIC MUST BE CLEARLY SHOWN AVOIDING THE |
| | UNDERGROUND INFRASTRUCTURE THAT IT CROSSES (EX: WATER, |
| | SANITARY, ELECTRIC, AND CABLE) AND THE EXISTING PALM |
| | TREE ROOT STRUCTURE. |
| | |