| Plan Review Notes For Permit 21120294 |
| Permit Number |
21120294 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-03 11:39:33 | 1. PROVIDED SURVEY IS NOT ACCURATE/COMPLETE. PLEASE | | | PROVIDE A COMPLETE SURVEY SHOWING THE FULL SCOPE OF | | | WORK. | | | | | | 2. PROPOSED BORE PITS AND HANDHOLE ARE TOO CLOSE TO | | | EXISTING PALM TREES, PLEASE ADJUST TO PROVIDE THE | | | NECESSARY SPACING TO PROTECT ROOT/TREE VIABILITY. | | | RECOMMENDED AT LEAST 8 FT. CLEARANCE FROM PALMS TO | | | SAFELY PROVIDE A BUFFER TO THE ROOT SYSTEM. | | | | | | 3. POLE & UNDERGROUND ELECTRIC SHOWN ON DRAWINGS TO | | | CONFLICT WITH EXISTING SANITATION/SEWER LINE, PLEASE | | | PROVIDE THE NECESSARY PUBLIC UTILITY LETTERS GRANTING | | | APPROVAL OF THIS PROPOSED BORE PITS, UNDERGROUND | | | ELECTRIC, AND POLE LOCATION. | | | | | | 4. PROPOSED UNDERGROUND ELECTRIC RUNS THROUGH PRIVATE | | | PROPERTY, REQUIRES AN UTILITY EASEMENT, OR REROUTE | | | THROUGH THE PUBLIC ROW. | | | | | | 5. THE POLE STEALTH DESIGN MEETS CITY STANDARDS. | | | | | | | | | CHRIS KIMMERLY @ (561)822-1426 | | | [email protected] | | | |
|