| Plan Review Notes For Permit 21120284 |
| Permit Number |
21120284 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-23 17:05:33 | 1) PROPOSED ELECTRIC AND POLE LOCATION DOES NOT APPEAR | | | TO BE IN CONFLICT WITH CITY UTILITIES HOWEVER CITY | | | UTILITIES ARE SHOWN INCORRECTLY ON PLANS. INCLUDE CITY | | | UNDERGROUND UTILITIY PIPE SIZE, PIPE MATERIAL, AND | | | DESCRIPTION ON THE SITE PLAN. CONTACT JANICE TARBILL, | | | [email protected] FOR AS-BUILT INFORMATION. INCLUDE | | | AS-BUILT INFORMATION IN YOUR RESUBMITTAL. | | | 2) PROVIDE PROFILE FOR PROPOSED UNDERGROUND ELECTRIC | | | SHOWING ALL CROSSING DATA FOR OTHER UTILITIES. | | | 3) ALL ROADWAY, SIDEWALK, AND SWALE RESTORATIONS ARE | | | REQUIRED PER CITY STANDARD. | | | | | | SUZANNE BERGLUND | | | [email protected] | | | 561-494-1075 | | | |
|