| Notes |
| Date |
Text |
| 2022-03-07 15:42:51 | INSUFFICIENT | | | | | | 1) THE BORE PIT NOTES ON SHEET P-1 STATE THAT THE | | | SIDEWALK WILL BE RESTORED; HOWEVER, THE PARKWAY WILL | | | ALSO NEED RESTORATION. PLEASE UPDATE THE NOTATIONS | | | ACCORDINGLY. | | | | | | 2) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC | | | WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH | | | EXISTING UTILITIES. | | | | | | 3) THE PLANS SHOW A GAS LINE WITHIN 2 FEET OF THE POLE | | | AND A BORE PIT DIG. IN ORDER TO VERIFY THAT THE | | | INSTALLATION WILL NOT INTERFERE WITH THE EXISTING | | | FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO | | | OBJECTION FROM FPU. | | | | | | 4) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. | | | THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP | | | 7042 TRAFFIC GREY A. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|