| 2021-12-29 10:35:24 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21120201 |
| | 12/29/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED PLAN IS LABELED MULTIFAMILY REMODELING |
| | HOWEVER NO REMODELING PLANS HAVE BEEN SUBMITTED- SEC. |
| | 107.2.1 WPB. |
| | |
| | 2) REFER TO SEC. 1010.1 FBC EX: THE CHANGE OF OCCUPANCY |
| | TO R WILL REQUIRE COMPLIANCE WITH TABLE 403.1 FBC P. |
| | PLEASE PROVIDE A SCHEDULE INDICATING THE REQUIRED AND |
| | PROVIDED NUMBER OF PLUMBING FIXTURES FOR THE PROPOSED |
| | OCCUPANCY. |
| | |
| | 3) THE CHANGE OF USE TO A MULTIFAMILY DWELLING WILL |
| | REQUIRE INSTALLATION OF A POTABLE WATER SERVICE |
| | BACKFLOW PREVENTER DEVICE IN ACCORDANCE WITH THE WPB |
| | DEPT. OF UTILITIES CROSS-CONNECTION CONTROL MANUAL. |
| | PLEASE NOTE A SEPARATE PERMIT WILL BE REQUIRED TO |
| | INSTALL A REDUCED PRESSURE ZONE (RPZ) BACKFLOW AT THE |
| | WATER METER- CHAPTER C (PAGE 12 WPB CROSS-CONNECTION |
| | MANUAL. |
| | A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | PLEASE NOTE ADDITIONAL COMMENTS MAY OCCUR UPON REVIEW |
| | OF RESUBMITTED PLANS. WHEN RESUBMITTING, IT IS HELPFUL |
| | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE CITY RE-SUBMITTAL FORM. |
| | |