| 2022-01-03 10:43:47 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF |
| | DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; 2.2.5 |
| | OF PAGE #5 PRODUCT APPROVAL FL38019-R2 INSTALLATION |
| | INSTRUCTIONS REQUIRE 2% POSITIVE SLOPE =1/4?/FT. |
| | ROOF/DECK DO NOT MEET THIS REQUIREMENT & DEC-TEC CAN |
| | NOT BE USED. |
| | 2. FBC EB 706.3(1) & 2.2.6 PAGE #5 PRODUCT APPROVAL |
| | FL38019-R2 PROVIDE A SIGNED AND SEALED MOISTURE REPORT |
| | PREPARED BY A FLORIDA REGISTERED DESIGN PROFESSIONAL. |
| | 3. FBC B 107.2.1. AS PER 2.2.7 PAGE #5 PRODUCT APPROVAL |
| | FL38019-R2 REVISE ROOF DIAGRAM/SKETCH TO INCLUDE |
| | STRUCTURAL DEFLECTION, VENTILATION AS PER2.2.8 & |
| | DRAINAGE AS PER 2.2.9. |
| | 4. FBC B 107.2.1. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |