| 2022-04-15 18:27:00 | ROOFING REVIEW: |
| | |
| | ORIGINAL COMMENT: |
| | 1- FLAT ROOF NOA 15-1020.02 SUBMITTED: |
| | CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS GOING TO BE |
| | INSTALLED. IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. SEE GENERAL |
| | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. |
| | NOTE: FASTENING OPTIONS WITH GENERAL LIMITATION #9 CAN |
| | NOT BE USED IF THEY DON'T MEET THE DESIGN PRESSURES OF |
| | ALL ROOF ZONES. SEE GENERAL LIMITATION #9 ON LAST PAGE |
| | OF NOA. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | NOTE: LOOKING AT THE NOA FOR THE SECOND TIME, I |
| | REALIZED THIS NOA IS FOR RECOVER DECK APPLICATIONS NOT |
| | FOR NEW CONSTRUCTION. I APOLOGIZE. NEED TO PROVIDE |
| | PRODUCT APPROVAL FOR WOOD DECKS AND THE SAME COMMENTS |
| | APPLY. NEED TO SPECIFY THE ASSEMBLY TO BE INSTALLED. |
| | THIS CAN BE SUBMITTED FOR REVIEW LATER AS A DEFERRED |
| | SUBMITTAL. ADVICE IF SUBMITTING LATER. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR |
| | SINGLE HUNG WINDOWS. PLANS DON'T SHOW ANY. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |