| Plan Review Notes For Permit 21120140 |
| Permit Number |
21120140 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-01-28 16:38:53 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) INSTALLATION DOES NOT COMPLY WITH 620.37(A) CO-AX | | | SERVES THE BUILDING. | | | | | | 620.37 WIRING IN HOISTWAYS, MACHINE ROOMS, CONTROL | | | ROOMS, MACHINERY SPACES, AND CONTROL SPACES. | | | (A) USES PERMITTED. ONLY SUCH ELECTRICAL WIRING, | | | RACEWAYS, AND CABLES USED DIRECTLY IN CONNECTION WITH | | | THE ELEVATOR OR | | | DUMBWAITER, INCLUDING WIRING FOR SIGNALS, FOR | | | COMMUNICATION WITH THE CAR, FOR LIGHTING, HEATING, AIR | | | CONDITIONING, AND VENTILATING | | | THE ELEVATOR CAR, FOR FIRE DETECTING SYSTEMS, FOR PIT | | | SUMP PUMPS, AND FOR HEATING, LIGHTING, AND VENTILATING | | | THE HOISTWAY, | | | SHALL BE PERMITTED INSIDE THE HOISTWAY, MACHINE ROOMS, | | | CONTROL ROOMS, MACHINERY SPACES, AND CONTROL SPACES. | | | | | | 2) PLEASE PROVIDE A COST BREAKDOWN FOR LABOR AND | | | MATERIAL. |
|