2022-01-28 16:38:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) INSTALLATION DOES NOT COMPLY WITH 620.37(A) CO-AX
 SERVES THE BUILDING.
  
 620.37 WIRING IN HOISTWAYS, MACHINE ROOMS, CONTROL
 ROOMS, MACHINERY SPACES, AND CONTROL SPACES.
 (A) USES PERMITTED. ONLY SUCH ELECTRICAL WIRING,
 RACEWAYS, AND CABLES USED DIRECTLY IN CONNECTION WITH
 THE ELEVATOR OR
 DUMBWAITER, INCLUDING WIRING FOR SIGNALS, FOR
 COMMUNICATION WITH THE CAR, FOR LIGHTING, HEATING, AIR
 CONDITIONING, AND VENTILATING
 THE ELEVATOR CAR, FOR FIRE DETECTING SYSTEMS, FOR PIT
 SUMP PUMPS, AND FOR HEATING, LIGHTING, AND VENTILATING
 THE HOISTWAY,
 SHALL BE PERMITTED INSIDE THE HOISTWAY, MACHINE ROOMS,
 CONTROL ROOMS, MACHINERY SPACES, AND CONTROL SPACES.
  
 2) PLEASE PROVIDE A COST BREAKDOWN FOR LABOR AND
 MATERIAL.