| Plan Review Notes For Permit 21120100 |
| Permit Number |
21120100 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-18 10:03:53 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, THE MARKED UP TABLE ON SHEET 13 OF 17 | | | FOR THE ACCORDIANS (P.A. #FL16893 R6) NEEDS TO BE | | | CORRECTED AS THERE APPEARS TO BE MISTAKES FOR THE | | | FASTENER TYPE BEING USED. | | | THE WPB SCHEDULE INDICATES (OPENINGS #1 & 5) THAT DUE | | | TO A WOOD SUBSTRATE, THE FASTENERS ARE TO BE WOOD | | | ANCHORS. THE INDICATED ANCHORS WITHIN THE PRODUCT | | | APPROVAL ARE FOR CONCRETE. | | | THE MISTAKE APPEARS TO BE BETWEEN MOUNT TYPE AND | | | FASTENER TYPE. |
|