| 2022-03-22 14:08:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION ON THE APPLICATION OF |
| | BATHROOM REMODEL, CHANGE TUB TO SHOWER. |
| | |
| | THERE IS ALSO A FLOOR PLAN SUBMITTED BUT IT DOES NOT |
| | INDICATE WHICH BATHROOM, OR BOTH, IS TO BE CHANGED. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.11 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION, |
| | MODIFICATION, OR REHABILITATION, CONSTRUCTION DOCUMENTS |
| | AND SHOP DRAWINGS SHALL BE SUBMITTED, REVIEWED, AND |
| | APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN |
| | SECTION 1.14. |
| | |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE INDICATE WHICH BATHROOM |
| | OR BOTH IS TO BE BE CHANGED ON THE FLOOR PLAN. |
| | |
| | |
| | 1A) THE FLOOR PLAN INDICATES THAT EACH BATHROOM WALL |
| | NEXT TO THE TUBS MAY BE FIRE RATED TENANT/CORRIDOR |
| | WALLS. |
| | |
| | ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED, |
| | ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGMENT. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |