| Plan Review Notes For Permit 21120095 |
| Permit Number |
21120095 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-27 16:53:45 | CHANGE BATH TO SHOWER - | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE CIRCLE ON THE FLOOR PLAN WHICH TUB IS BEING | | | CONVERTED TO A SHOWER | | | | | | 2) PLEASE SHOW THE GRAB BAR BACKING DETAILS FOR THE | | | SHOWER TO COMPLY WITH FBC FHA | | | | | | REQUIREMENT 6 -REINFORCED WALLS FOR GRAB BARS. | | | SECTION 100.205(C)(3)(III)REQUIRES THAT COVERED | | | MULTIFAMILY DWELLINGS WITH A BUILDING ENTRANCE ON AN | | | ACCESSIBLE ROUTE SHALL BE DESIGNED AND CONSTRUCTED IN | | | SUCH A MANNER THAT ALL PREMISES WITHIN COVERED | | | MULTIFAMILY DWELLING UNITS CONTAIN REINFORCEMENTS IN | | | BATHROOM WALLS TO ALLOW LATER INSTALLATION OF GRAB BARS | | | AROUND TOILET, TUB, SHOWER STALL AND SHOWER SEAT, WHERE | | | SUCH FACILITIES ARE PROVIDED. | | | | | | GUIDELINE | | | | | | REINFORCED BATHROOM WALLS TO ALLOW LATER INSTALLATION | | | OF GRAB BARS AROUND THE TOILET, TUB, SHOWER STALL AND | | | SHOWER SEAT, WHERE SUCH FACILITIES ARE PROVIDED, WOULD | | | MEET SECTION 100.205(C)(3)(III) IF REINFORCED AREAS ARE | | | PROVIDED AT LEAST AT THOSE POINTS WHERE GRAB BARS WILL | | | BE MOUNTED. (FOR EXAMPLE, SEE FIG. 3, 4 AND 5.) |
|