| 2021-12-21 14:25:14 | FAILED SECOND ELECTRIC REVIEW |
| | |
| | 1) PROVIDE CLARITY IN DOCUMENTS SUBMITTED. INCLUDE |
| | EQUIPMENT, CONDUCTORS WIRING METHODS, NOTING WHAT IS |
| | NEW AND WHAT IS EXISTING FROM POINT OF ORIGIN TO |
| | UTILIZATION EQUIPMENT. DETAIL EXISTING LOADS AND LOAD |
| | CALCULATIONS FOR ALL EQUIPMENT WHETHER EXISTING OR NEW. |
| | THE WORK SCOPE FOR THE PROJECT STATES" INSTALL SERVICE |
| | WIRES FROM METER CAN TO NEW 200 AMP PANEL AND INSTALL |
| | GFI RECEPTACLE FOR TEMPORARY POWER" IF THIS IS |
| | INACCURATE THEN PLEASE SUBMIT A CORRECT WORK SCOPE. FBC |
| | 107.2 |
| | |
| | 2) VALUE IS STATED AT $650. PLEASE PROVIDE AN ACCURATE |
| | VALUATION FOR PROJECTS SUBMITTED AS PER THE W.P.B. |
| | AMENDMENT 109.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |