| 2021-12-29 07:08:44 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21120091 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ORIGINAL SUBMITTAL HAS A MANUAL J CALCULATION | | | THAT REQUIRED A 5000 BTU UNIT AND AN 8000 BTU UNIT. | | | THIS SUBMITTAL IS FOR 2 8000 BTU UNITS. PLEASE PROVIDE | | | AN UPDATED MANUAL J CALCULATION SHOWING THIS CHANGE. | | | THE WINDOW UNITS USED TO CONDITION THE SPACES IS FOR | | | A/C ONLY. PLEASE PROVIDE UNITS THAT MEET THE HEATING | | | REQUIREMENTS OF FBC RES R303.10. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|