| Plan Review Notes For Permit 21120055 |
| Permit Number |
21120055 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-29 10:40:10 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21120055 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THERE ARE 3- EF-1 EXHAUST FANS BUT THEY ARE NOT | | | SHOWN ON THE DETAILS AND NOTES SHEET. PLEASE PROVIDE | | | THE DETAILS FOR THESE EXHAUST FANS INCLUDING THE | | | EXHAUST CFM?S MAKING SURE THEY MEET THE REQUIREMENTS OF | | | FBC M TABLE 403.3.1.1 FOOTNOTE E. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|