| 2022-02-09 09:22:24 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) THIS PROJECT IS |
| | PERMITTED UNDER THE 2017 FBC. |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE ADDRESS OF THIS PROJECT IS 345 BANYAN. THE |
| | ADDRESS ON THE SHOP DRAWINGS IS 303 BANYAN WHICH IS NOT |
| | CORRECT. PLEASE CORRECT. FBC 107.2.1 |
| | |
| | 2) THIS PROJECT IS PERMITTED UNDER THE 2017 FBC AND |
| | ASCE 7-10. SEE SHEETS ALS.0.1 & S.005 OF MASTER PERMIT |
| | #20101431. THE NOTE ON SHEET 0.00 OF THE WINDOW SHOP |
| | DRAWINGS STATES THAT THE STRUCTURAL FRAMING WAS |
| | DESIGNED USING THE FBC 2020. THE SAME CODE IS REQUIRED |
| | TO BE USED THROUGHOUT THE CONSTRUCTION OF THE BUILDING. |
| | PLEASE CORRECT. |
| | |
| | 2) THERE ARE NO SHOP DRAWING REVIEW STAMPS FROM THE |
| | DESIGNER OF RECORD OR THE CONTRACTOR ON THE WINDOW SHOP |
| | DRAWINGS OR THE CALCULATIONS FOR THE EXTERIOR GLAZING |
| | SYSTEMS. YOU CAN MAKE A COPY OF THE COVERSHEET TO PUT |
| | THE STAMPS ON SO THAT THE DIGITALLY SIGNED DOCUMENTS |
| | ARE NOT CORRUPTED OR USE A TRANSMITTAL DOCUMENT THAT |
| | LISTS THE SPECIFIC PAGES CONTAINED IN THE DOCUMENTS. |
| | FBC AMENDMENTS 107.3.4 |
| | |
| | 3) LARGE MISSILE IMPACT GLAZING IS REQUIRED IN OPENINGS |
| | LOCATED WITHIN 30 FEET OF GRADE. FBC 1609.1.2 |
| | |
| | 4) THE BUILDING OFFICIAL HAS NOT PREVIOUSLY APPROVED |
| | MAXIMUM DESIGN PRESSURES OF PRODUCTS THAT ARE WITHIN 5% |
| | OF THE REQUIRED WINDLOAD PRESSURES. SUBMIT PRODUCT |
| | APPROVALS WITH MAXIMUM DESIGN PRESSURES THAT MEET OR |
| | EXCEED THE REQUIRED COMPONENT AND CLADDING WIND LOAD |
| | PRESSURES FOR THE OPENINGS. FBC 1609.1 |
| | |
| | 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |