Plan Review Notes
Plan Review Notes For Permit 21120015
Permit Number 21120015
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-01 14:01:53PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1:
  
 1.) SPECIFY THE DATES OF INSTALLATION AND REMOVAL FOR
 TENTS.
 2.) PROVIDE THE ESTIMATED OCCUPANCY OF EACH TENT.
 3.) PROVIDE THE ACCESSIBLE ROUTE FROM TENTS TO
 ACCESSIBLE RESTROOMS (MUST BE WITHIN 500' DISTANCE).
 4.) THE NOTE ON THE ENGINEER'S SUBMITTALS NEEDS TO BE
 CHANGED FROM (FABRIC TO BE REMOVED IF WINDS EXCEED 75
 MPH) TO (FABRIC TO BE REMOVED IF WINDS EXCEED 30 MPH.)