| 2022-03-15 14:46:16 | FAILED |
| | |
| | 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT |
| | PERMIT - CITY RIGHTS-OF-WAY (19070659) MUST BE UPLOADED |
| | TO PROJECT DOX AND APPROVED PRIOR TO THIS PERMIT BEING |
| | APPROVED. |
| | |
| | 2) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED |
| | SURVEYOR, WHICH SHOWS THE POLE LOCATION AND THE |
| | RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE |
| | WIRELESS COMMUNICATION FACILITY IS WITHIN THE |
| | RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY. THE SURVEY |
| | MUST PROVIDE THE DIMENSION FROM THE PROPERTY LINE TO |
| | THE BACK OF CURB SO THAT STAFF CAN VERIFY THAT THERE IS |
| | PROPER ADA CLEARANCE AND THAT THE POLE AND ITS |
| | FOUNDATION ARE FULLY IN THE RIGHT-OF-WAY. |
| | |
| | 3) STAFF HAS REVIEWED THE POLE AND FOUNDATION DETAILS |
| | AND IT APPEARS THAT THE DIMENSIONS ON THE SITE PLAN AND |
| | IT APPEARS THAT IF THE SITE PLAN DIMENSION IS USED, THE |
| | SIDEWALK MAY NOT BE WIDE ENOUGH TO MEET ADA SIDEWALK |
| | CLEARANCE. HOWEVER, WHEN USING THE 2.5-FOOT FOUNDATION |
| | LISTED IN THE POLE ENGINEERING PLUS THE BASE PLATE, |
| | THERE IS SUFFICIENT ADA CLEARANCE. ALL PLANS NEED TO |
| | SHOW ACCURATE CONDITIONS. |
| | |
| | 4) PROVIDE THE RESTORATION DETAILS FOR THE PROPOSED |
| | BORE PITS AND HANDHOLES. |
| | |
| | 5) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC |
| | WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH |
| | EXISTING UTILITIES. |
| | |
| | 6) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. |
| | THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP |
| | 7042 TRAFFIC GREY A. |
| | |