Plan Review Notes
Plan Review Notes For Permit 21111282
Permit Number 21111282
Review Stop G
Sequence Number 1
Notes
Date Text
2022-06-21 11:41:481ST REVIEW FBC-2020 RES.
 PERMIT- 21111282
 6/21/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 GRILL THAT INDICATES THE MAKE AND MODEL NUMBER, NATURAL
 OR LP GAS FIRED, AND THE BTU LOAD OF THE APPLIANCE-
 G2408.1 & G2447.1 FBC RES. A) FOR NATURAL GAS
 INSTALLATIONS PLEASE CLARIFY IF NEW GAS PIPING IS BEING
 INSTALLED TO SUPPLY THE GRILL. OR IF THERE IS AN
 EXISTING PIPE THROUGH THE WALL BEHIND THE GRILL. PLEASE
 PROVIDE THE TYPE, SIZE, AND SUPPLY PRESSURE OF THE
 EXISTING PIPE IF APPLICABLE, OR PROVIDE A COMPLETE GAS
 RISER FOR NEW INSTALLATIONS- SEC. 107.2.1 & 107.3.5.3
 WPB.
  
 2) REFER TO THE MANUFACTURER'S SPECIFICATIONS AND SHOW
 THE LOCATIONS AND SIZES OF COMBUSTION AIR AND
 VENTILATION OPENINGS- SEC. G2407.1 FBC RES.
  
 3) PLEASE PROVIDE ON THE SURVEY OR ON A SITE PLAN THE
 EXACT LOCATION OF THE GRILL. PLEASE NOTE THAT MANY OF
 THE GRILL MANUFACTURER'S DO NOT ALLOW INSTALLATIONS IN
 ENCLOSED OR PARTIALLY ENCLOSED STRUCTURES WITH OVERHEAD
 CONSTRUCTION UNLESS A HOOD AND EXHAUST VENT SYSTEM IS
 INSTALLED- G2408.1 & G2447.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  