Plan Review Notes
Plan Review Notes For Permit 21111274
Permit Number 21111274
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-01-28 12:51:031. THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH
 THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED
 WITH THE AFOREMENTIONED PERMIT.
  
 2. PROVIDED SURVEY IS NOT ACCURATE/COMPLETE. PLEASE
 PROVIDE A COMPLETE SURVEY SHOWING FULL SCOPE OF WORK.
  
 3. PLEASE PROVIDE THE NECESSARY PUBLIC UTILITY LETTERS
 GRANTING APPROVAL OF THE BORE PITS, HANDHOLES, AND
 UNDERGROUND ELECTRICAL FOR THIS PROPOSED POLE LOCATION.
  
 4. PROPOSED BORE PITS AND HANDHOLE ARE TOO CLOSE TO
 EXISTING PALM TREES, PLEASE ADJUST TO PROVIDE THE
 NECESSARY SPACING TO PROTECT ROOT/TREE VIABILITY.
 RECOMMENDED AT LEAST 8 FT. CLEARANCE FROM PALMS TO
 SAFELY PROVIDE A BUFFER TO THE ROOT SYSTEM.
  
 5. PROPOSED UNDERGROUND ELECTRIC RUNS THROUGH PRIVATE
 PROPERTY, REQUIRES A UTILITY EASEMENT, OR REROUTE
 THROUGH THE PUBLIC ROW.
  
 6. THE POLE STEALTH DESIGN MEETS CITY STANDARDS.
  
  