2022-01-21 11:26:44RESIDENTIAL (R3) ALTERATION/ADDITION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21111240
  
 NOTE:
 ADDITION SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- THERE IS NOT INFORMATION FOR THE CONSTRUCTION OF THE
 "OPEN LATTICE WALL" SHOWN ON TWO SIDES OF CARPORT.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW
 THIS WALL WILL RESIST THE WIND LOADS. SEC. R301.2.1
 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR THE
 INSTALLATION OF THE ALUMINUM GATE TO THE STRUCTURE.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 3-LOW SLOPE ROOFS: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR OVERFLOW DRAINS OR SCUPPERS AS
 REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL.
 PROVIDE DETAILS: SPECIFY SIZE AND LOCATION ON ROOF.
  
 4- PRESSURE ZONES DETAIL 4 ON SHEET A-1:
 A)THE SPECIFIED DESIGN PRESSURES ARE TOO LOW FOR
 COMPONENTS AND CLADDING LOADS. REVISE AS REQUIRED BY
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 B)CLARIFY ROOF DIAGRAM ROOF ZONES. SPECIFY WHAT IS THE
 DIMENSION FOR "A". SEE FIGURE R301.2(7)
 FBC-RESIDENTIAL. CLARIFY WHY DESIGN PRESSURES FOR ZONE
 3' ARE LOWER THAN DESIGN PRESSURES FOR ZONE 3 IF IT
 LOOKS LIKE ROOF ZONE IS THE OUTER CORNER. ALSO, WHERE
 ARE ROOF ZONES 3' AND 3 COMING FROM?. SEC. R301.2.1
 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 5- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR STEEL
 COLUMN TOP CONNECTION. ONLY BASE CONNECTION WAS
 PROVIDED. SEC. R301.1 FBC-RESIDENTIAL
  
 6- REVISE ROOFING SPECIFICATIONS SHOWN ON SECTION
 DETAIL 5 ON SHEET A-2. DESIGN PRESSURES ARE HIGHER THAN
 -90PSF ON ROOF ZONE 3. COORDINATE WITH ITEM #4 ABOVE.
  
 7- FLAT ROOF NOA 17-1003.04: SELECTED ASSEMBLY ON PAGE
 33 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF
 ZONES. REVISE ASSEMBLY FOR ONE THAT MEETS THE DESIGN
 PRESSURES FOR ALL ROOF ZONES OR SELECT ANY ASSEMBLY
 WITH GENERAL LIMITATION #7 THAT ALLOW FOR NAIL
 ENHANCEMENT. SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED. SEE GENERAL LIMITATIONS #9 AND #7 ON LAST
 PAGE OF NOA.
 NOTE: COORDINATE WITH ITEMS #4 AND #6 ABOVE.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE REVISED PRODUCT
 APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  