| 2021-12-15 14:57:00 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21111211 |
| | 12/15/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P2.1 & P5.1: THE ISO SHOWS THE SINK PUMP VENT |
| | PIPE CONNECTING TO THE EXISTING RISER BUT SINK PUMP |
| | DETAIL SHOWS AN AAV- WHICH IS CORRECT?- SEC 906.5 FBC |
| | P. |
| | |
| | 2) P2.1: PLEASE SHOW THE LOCATIONS OF THE REQUIRED |
| | CHECK VALVE AND FULL OPEN VALVES ON THE DISCHARGE PIPE, |
| | AND SHOW HOW ACCESS TO THE VALVES WILL BE PROVIDED- |
| | SEC. 712.2 FBC P. |
| | |
| | 3) A1.1: SHOW THE CLEAR FLOOR SPACE APPROACH DIAGRAMS |
| | AND DIMENSIONS AT WATER DISPENSER, DISHWASHER AND |
| | REFRIGERATOR- SECTIONS 305, 804.6.3 & 804.6.6 FBC ACC. |
| | |
| | 4) A1.1 & A3.2: PROVIDE AN ELEVATION DETAIL OR NOTE TO |
| | VERIFY THE FREEZER INSIDE THE REFRIGERATOR HAS A |
| | MINIMUM OF 50 PERCENT OF FREEZER SPACE 54-INCHES |
| | MAXIMUM FROM THE FINISHED FLOOR. |
| | |
| | D) A1.1 & A3.2: SHOW THE HEIGHT OF THE WATER DISPENSER |
| | CONTROL AND INDICATE COMPLIANCE WITH SEC. 308- REACH |
| | RANGES, AND 309- OPERABLE PARTS. PLEASE SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS FOR THE DISPENSER |
| | INDICATING ADA COMPLIANCE- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |